Residential · Virtual lab · Beginner · about 16 minutes
The 120/240 V Service: A Split-Phase Laboratory
Every house gets both of its voltages from one transformer winding with a tap in the middle. Put a meter on the service below, guess each reading before it shows, load the two legs, then break the neutral and watch what happens to the lamps.
You will learn:
- Why one center-tapped winding gives two 120 V legs that are 240 V apart
- What the neutral carries, and why balanced legs leave it nearly idle
- How to read a meter between legs, neutral, ground and earth, and what each reading means
- Why a 240 V load puts nothing on the neutral
- What an open neutral does to the loads on each leg
What this model assumes
- Loads are resistive and in phase, so the currents of the two legs subtract arithmetically on the neutral. Motors, dimmers and electronic loads draw current out of phase and in pulses, and their neutral currents do not cancel as neatly.
- Every conductor has a fixed small resistance (0.02 ohms per service conductor), which is why the simulator reads a volt or so under the nominal figures when loads are on.
- The earth is modeled as 25 ohms at each electrode. With the neutral open it becomes a 50 ohm return path, which is why the simulator's open-neutral voltages sit a little closer together than the ideal arithmetic.
- Readings are RMS values, the ones a meter reads, and the model has no time: every reading is the steady state.
One winding, two legs
Almost every house in North America is fed from one transformer winding. The utility transformer on the pole or in the green box on the lawn steps the distribution voltage down to 240 V across a single secondary winding, and that winding has a connection brought out from its exact middle, the center tap. The two ends of the winding are the two hot conductors, called leg 1 and leg 2 in this lesson and bus A and bus B once they reach the panel. The center tap is the neutral. It is connected to the earth at the transformer and again at the service, which is why it is also called the grounded conductor.
Measure from either end of the winding to the center tap and you read half the winding, 120 V. Measure from one end to the other and you read the whole winding, 240 V. That is the entire trick of a split-phase service: one winding, tapped in the middle, gives a house both voltages. Small loads such as lights, receptacles and electronics connect from one leg to the neutral for 120 V. Large loads such as a range, a dryer, a water heater, an air conditioner or an EV charger connect from leg to leg for 240 V and do not use the neutral at all.
The two legs are two ends of the same coil, so they are not two separate sources. At the instant leg 1 is at its positive peak against the neutral, leg 2 is at its negative peak. That is what lets the voltages add to 240 V between the legs, and it is also why a 120 V load on each leg sends its return current the opposite way along the neutral. The two return currents meet at the neutral bar and cancel, so the neutral carries only the difference between the two legs. Balance the legs and the neutral is nearly idle. Load one leg heavily and the other lightly and the neutral works hard.
Follow the service from the pole to the panel
The drawing below follows the three service conductors from the transformer, through the meter and into the panel. Switch to the exploded view to pull the pieces apart, and tap any piece, or its name in the list, to read what it does, how it is marked and where it fails.
Interactive: From the transformer to the panel
Three markings matter. On the transformer the secondary bushings are X1, X2 and X3, with X2 the center tap. In the panel the two hots land on the main breaker and become the two bus bars, and the neutral lands on the neutral bar, which at the service is bonded to the enclosure by the main bonding jumper. From that bar the grounding electrode conductor runs to the ground rod or another electrode. The grounding lesson follows that path further; here it matters because it is what holds the neutral at earth potential, and it is why a meter from the neutral bar to the ground bar reads zero.
Before you touch anything, predict
The laboratory below starts with a 1,500 W space heater on leg 1 and a 100 W lamp on leg 2. Commit to an answer for each question, then go and test it.
Predict first
The lamp is moved from leg 2 to leg 1, the same leg as the heater. What happens to the current on the service neutral?
- It falls to zero, because both loads are on one leg
- It stays about the same, around 11.7 A
- It rises to the sum of the two loads, about 13.3 A
- It becomes 240 V
What happens
With both loads on leg 1 there is nothing on leg 2 to cancel against, so the neutral carries the whole return current of both loads, 12.5 A plus 0.83 A. The difference rule only reduces the neutral current when the loads sit on opposite legs. Try it: switch the lamp to leg 1 in the laboratory and watch the neutral reading.
Predict first
The service neutral breaks at the pole with the 1,500 W heater on leg 1 and the 100 W lamp on leg 2. Which load sees the higher voltage?
- The heater, because it is the bigger load
- The lamp, the smaller load
- Both stay at 120 V, because the legs still have their hots
- Both drop to about 60 V
What happens
With the neutral gone the two loads sit in series across 240 V, and in a series circuit the larger resistance takes the larger share of the voltage. The 100 W lamp is 144 ohms and the heater is 9.6 ohms, so the lamp takes most of the 240 V and the heater is left with a few volts. Try it: pick the open neutral scenario and put the meter across the lamp.
The service laboratory
The laboratory is the service drawn as a circuit: the two halves of the transformer winding, the three service conductors, the neutral and grounding bars, the ground rod, and four loads. Switch loads on and off, change the heater and kitchen watts, move the lamp between legs, open the neutral, and put the meter's two probes on any two points. The meter stays blank until you guess the reading, because the guess is where the learning happens.
Interactive: The 120/240 V laboratory
Things worth trying:
- Put the probes on bus A and the neutral bar, guess, then move the black probe to bus B. The reading doubles, because you are now across the whole winding.
- Put the probes on the neutral bar and the ground bar. Zero, because the bonding jumper joins them at the service. Then move the black probe to the earth and watch a fraction of a volt appear under load, which is the drop along the service neutral.
- Switch the kitchen outlets on and the lamp off. The two legs are nearly balanced and the neutral reading falls to under an amp.
- Switch the dryer on by itself. Both legs read the same current and the neutral reads nothing, because a 240 V load goes out on one leg and comes back on the other.
- Open the neutral with the heater and the lamp on. The lamp jumps past 200 V and the heater drops to about 30 V. Put the meter from the neutral bar to the earth: the neutral bar is no longer anywhere near earth potential.
Neutral current with a heater and a lamp
Given: 1,500 W space heater on leg 1; 100 W lamp on leg 2; Both are 120 V loads, resistive and in phase
- Heater current: 1,500 ÷ 120 = 12.5 A
- Lamp current: 100 ÷ 120 = 0.83 A
- Neutral current: 12.5 − 0.83 = 11.67 A
Answer: About 11.7 A on the neutral; the simulator reads 11.6 A because its conductors drop a volt under load
| Probes | Reading | Why |
|---|---|---|
| Bus A to neutral bar | 120 V | Half the winding |
| Bus B to neutral bar | 120 V | The other half |
| Bus A to bus B | 240 V | The whole winding |
| Neutral bar to ground bar | 0 V | Bonded together at the service |
| Bus A to ground bar | 120 V | The ground bar sits at neutral potential at the service |
| Neutral bar to earth | Under 1 V | The drop along the service neutral under load |
What the model leaves out
- Phase. The loads are resistive and in phase, so the neutral carries the plain difference. Motors, dimmers, LED drivers and computer supplies draw current out of phase and in pulses, and their neutral currents do not cancel as neatly.
- Conductor resistance. Each service conductor is 0.02 ohms, so the legs read a volt or so under 120 V with the heater on. Real drops depend on the conductor size and length, which the voltage drop lesson works through.
- The earth. The model gives each electrode 25 ohms, so with the neutral open there is still a 50 ohm path through the earth between the panel and the transformer. That is why the simulator's open-neutral readings, about 209 V on the lamp and 31 V on the heater, sit a little closer together than the ideal series arithmetic, which gives 225 V and 15 V. The earth path also carries about 1.8 A in that case, current through the ground rods that should never be there.
- Time. Every reading is the steady state. A real open neutral flickers as loads switch, and the voltages swing with every change.
Work the service
Three challenges, each checked against the same model as the laboratory.
Challenge: Find the part
The lesson names a part of the service, such as the center tap or the main bonding jumper, and you find it on the drawing or pick it from the list.
Challenge: What will the meter read?
Three probe placements on the normal service: pick the reading from 0, 120, 208 or 240 V, then see why.
Challenge: The open neutral
Two loads and a broken neutral: pick which load sees the higher voltage and about how much, for three pairs of loads.
A habit that helps on the job. Before trusting any reading, name the two points the probes are on and say what they should read. A meter is only right about the two points it touches, and the open neutral is the classic case where a reading that looks fine, 240 V between the legs, hides a problem that is cooking the lamps on one side of the house.
Where this shows up
Service work runs on this one drawing. A service upgrade from 100 A to 200 A, a panel change, a meter socket replacement, a new feeder to a subpanel: every one of them is the same three conductors and the same two readings, 120 V to the neutral and 240 V across. Electricians who do residential and service work read these voltages at the start of every job. The measurement itself is qualified work with a rated meter, and everything after it waits for the power to be off and verified off.
The open neutral is the service call to remember. Customers describe lights that brighten when the dryer starts, a television that died when the microwave ran, bulbs that burn out by the dozen, or a dimming on one side of the house and a brightening on the other. A reading of 240 V between the legs with 90 V on one leg and 150 V on the other, moving as loads switch, is the signature. The break can be at the panel, at the meter, at the weatherhead or at the transformer, and the utility owns part of that path, so the first call after the diagnosis is often to them.
If this is the work you want more of, the openings below are residential and service roles where the service entrance is the start of every day. The panel lesson picks up where the service conductors land, and the grounding lesson follows the neutral and the bonding jumper into the fault path.
Check your understanding
1. On a 120/240 V service, what does a meter read from one hot leg to the neutral?
Answer: 120 V. Each leg is one half of the center-tapped winding, so leg to neutral reads 120 V.
2. What does the meter read between the two hot legs, and why?
Answer: 240 V, because the legs are the two ends of one 240 V winding. The two legs are the ends of the same winding, so the meter reads the whole winding, 240 V. The 208 V figure belongs to three-phase wye systems.
3. A 1,500 W heater runs on leg 1 and a 100 W lamp on leg 2. About what current does the service neutral carry?
Answer: 11.7 A, the difference. The two return currents flow opposite ways on the neutral and cancel to the difference: 12.5 A minus 0.83 A is about 11.7 A.
4. A 5,400 W dryer element runs alone across both legs. What does the neutral carry from it?
Answer: Nothing. A 240 V load goes out on one leg and returns on the other, so the neutral carries nothing from it. Each leg carries 22.5 A.
5. The service neutral opens with the 1,500 W heater on leg 1 and the 100 W lamp on leg 2. Ignoring the earth path, about what voltage lands on the lamp?
Answer: 225 V. The two loads sit in series across 240 V. The lamp's 144 ohms takes 225 V and the heater's 9.6 ohms takes 15 V, which is why lamps burn out in a house with an open neutral.
Where this knowledge gets used
- Residential openings: Service upgrades, panel changes and meter work are everyday residential jobs.
- Service and repair openings: Service electricians diagnose open neutrals, dead legs and loose connections from these readings.
- Working as a journeyman: What journeyman electricians are expected to know and how the role grows.
Sources and further reading
Tony R. Kuphaldt (ibiblio)
Lessons In Electric Circuits (six volumes)Split-phase power systems and why the two legs are 180 degrees apart, Volume II chapter 10.
Global, physics and circuit theory; US examples. Volume editions dated per volume (DC 5th, AC 6th).
Fluke
Digital multimeter basics and troubleshootingHow a voltmeter reads between two points and the measurement categories a meter needs at a service.
Global. Current article.
National Fire Protection Association
NFPA 70, National Electrical Code (NEC)Article 230 services and 250.24, the grounded conductor at the service.
United States; adopted by jurisdiction. 2026 edition issued August 2025; the 2023, 2020 and 2017 editions remain in force in many states; each state adopts its own edition and amendments.