Home > Electrical Learning Lab > Electrical panels

Distribution · Lesson · Beginner · about 17 minutes

Electrical Panels and Circuit Protection

A panelboard takes one service and splits it into the circuits of a building, with a breaker protecting each one. Take a panel apart below, switch its circuits on and off, load them up and find out what each breaker does when the current goes wrong.

Builds on Series and parallel circuits.

You will learn:

  • What the main breaker, bus bars, neutral bar, grounding bar and bonding jumper each do
  • Why a one-pole breaker gives 120 V and a two-pole breaker gives 240 V
  • How 120 V loads on the two buses share the neutral
  • Why an overload trips after a delay and a fault clears at once
  • Reading a breaker's time-current curve
  • Why the drawings are an explanation and never a work procedure
What this model assumes
  • The service holds 120 V from each bus to the neutral and 240 V between the buses, whatever the load, and the conductors have no resistance.
  • Loads are resistive and in phase, so the currents on a bus add arithmetically and the neutral carries the plain difference between the two 120 V totals.
  • Breakers follow a smooth inverse-time curve above their rating and open within about one cycle at ten times it. Real breakers publish their own time-current curves, and those are the ones to use on the job.
  • GFCI and AFCI electronics are described in the parts list but are left out of the model.
Understand

What a panel does

Every building gets its power through one service, and almost nothing in the building runs on the whole service at once. The panelboard is where that one supply is divided into branch circuits, each sized for the loads it serves and each protected by its own circuit breaker. The breaker's first job is to protect the conductors of its circuit from carrying more current than they can handle. Protecting the appliance at the end is a bonus, and protecting people is the job of other devices described later.

A house in North America is fed by a 120/240 V split-phase service. The utility transformer has one 240 V winding with a tap in the middle. The two ends of the winding are the ungrounded (hot) conductors, and the center tap is the grounded conductor, the neutral. Measure from either hot conductor to the neutral and you read 120 V. Measure between the two hot conductors and you read 240 V, because they sit at opposite ends of the same winding.

Inside the panel those two hot conductors become two bus bars, called A and B in this lesson. Small loads such as lights and receptacles take 120 V from one bus and the neutral. Large loads such as a range, a dryer, a water heater or an air conditioner take 240 V from both buses, through a two-pole breaker. The example panel used throughout this lesson has a 200 A main breaker and six circuits down one column of eight positions.

Explore

Take a panel apart

The drawing below is a load center with its dead front removed, the way an electrician sees it with the power off. Switch to the exploded view to pull the pieces apart, and tap any piece, or its name in the list, to find out what it does and how it fails.

Interactive: Inside a panelboard

An exploded view of a residential 120/240 V load center: the service conductors, the main breaker, the two bus bars, the neutral bar, the equipment grounding bar, the main bonding jumper, one-pole and two-pole breakers, a GFCI breaker and the dead front. Each piece is named and explained. The simulator runs in your browser with JavaScript turned on.

Three bars do most of the work. The two bus bars carry the two hot conductors down the panel, and each breaker clips onto a stab from one bus or both. The neutral bar is where the white grounded conductors land, and it carries current back to the transformer. The equipment grounding bar is where the bare or green conductors land. In normal operation it carries nothing at all. Its job is to give a fault a low-resistance path back to the source so that a breaker trips quickly, and the main bonding jumper at the service is what connects that path to the neutral and the enclosure.

Understand

Two buses, one neutral

Positions down a column alternate between the two buses: the first position is on bus A, the second on bus B, the third on bus A again. A one-pole breaker in any position connects its circuit to one bus, so the circuit gets 120 V between that bus and the neutral. A two-pole breaker takes two adjacent positions, so it lands on bus A and bus B at once and delivers the 240 V between them. Real panels number their positions across two columns, but each column alternates the same way, and the rule is the same: adjacent positions, two different buses, 240 V.

The example panel: 200 A main, eight positions in one column
PositionCircuitBreakerBusVoltageTypical load
1Kitchen small appliance20 A, one poleA120 V12 A
2Bedroom outlets15 A AFCI, one poleB120 V6 A
3 and 4Range50 A, two poleA and B240 V32 A
5Bathroom20 A GFCI, one poleA120 V10 A
6Lighting15 A, one poleB120 V8 A
7 and 8Dryer30 A, two poleA and B240 V24 A

A 240 V load draws the same current from both buses and sends nothing back on the neutral, because its current goes out on one hot conductor and comes back on the other. A 120 V load draws from one bus and returns on the neutral. When both buses carry 120 V loads at the same time, their return currents flow in opposite directions on the neutral and partly cancel, so the service neutral carries only the difference. That is why electricians balance 120 V circuits between the buses when they plan a panel.

What the service neutral carries

Given: 120 V loads on bus A: kitchen 12 A and bathroom 10 A, 22 A in all; 120 V loads on bus B: bedrooms 6 A and lighting 8 A, 14 A in all; 240 V loads: range 32 A and dryer 24 A, which return on the other hot conductor

  1. Bus A current: 12 + 10 + 32 + 24 = 78 A
  2. Bus B current: 6 + 8 + 32 + 24 = 70 A
  3. Neutral current: 22 − 14 = 8 A
  4. Main loading: 78 ÷ 200 = 39 percent

Answer: 78 A on bus A, 70 A on bus B, 8 A on the neutral, 39 percent of the main

Experiment

Load the panel

The simulator runs the example panel. Switch breakers on and off, set each circuit's load and watch the two bus currents, the neutral current and the main loading follow. Tap a position on the drawing to see which bus it sits on and what voltage it delivers. Raise the kitchen circuit past 20 A and the breaker's thermal memory begins to climb; speed time up and it trips after a few minutes. Pick the fault scenario and the dryer breaker opens before you can read the current.

Interactive: A working 120/240 V panel

The example panel with a main breaker and six branch circuits. Each breaker can be switched, each circuit's load can be set, and readings show the current on bus A, bus B and the neutral and the main loading. An overloaded breaker trips after the delay its curve allows; a fault trips the breaker at once. Tapping a position reports its bus and voltage. The simulator runs in your browser with JavaScript turned on.

Two things worth trying. Move 120 V load from one bus to the other with the switches and watch the neutral current rise as the buses go out of balance. Then load the kitchen circuit to 24 A and leave it: the breaker holds for about seven minutes on the lesson's curve before it trips, which is how a breaker rides through a brief surge and still catches a circuit that is slowly overloaded.

Understand

Overload or fault? Two problems, two elements

A breaker opens for two different reasons, and it uses a different element for each. An overload is more current than the circuit is rated for, flowing through the normal path: a space heater and a hair dryer on the same 15 A circuit, or a receptacle circuit feeding a shop full of tools. The current is a little above the rating and the danger is heat building up in the conductors over minutes. The breaker's thermal element, a bimetal strip that bends as it warms, handles this. The more the current exceeds the rating, the faster it trips.

A short circuit or a ground fault is current taking a path it should never take: hot to neutral, hot to hot, or hot to the enclosure, a box or a water pipe. With almost no resistance in the path, the current is limited only by the service, so it can be thousands of amps, and the damage is done in a fraction of a second. The breaker's magnetic element, a coil that pulls the trip mechanism when the current is far above the rating, handles this in about one cycle. For a ground fault, the equipment grounding conductor and the main bonding jumper are what make that current flow at all; without that path back to the source, a fault to a metal box would just leave the box energized, which is why grounding and bonding are checked by qualified people before a panel is energized and never bypassed.

Trip times from the lesson's curve, 20 A breaker
CurrentMultiple of ratingTime to trip
20 A or less100 percentNever
24 A120 percentAbout 7 minutes
27 A135 percentAbout 4 minutes
40 A200 percentAbout 1 minute
200 A or more1,000 percentAbout one cycle

A space heater on a loaded circuit

Given: 20 A kitchen circuit already carrying 12 A; A 1,500 W space heater is plugged in: 1,500 ÷ 120 = 12.5 A

  1. Total current: 12 + 12.5 = 24.5 A
  2. Multiple of rating: 24.5 ÷ 20 = 1.23
  3. On the lesson's curve, 123 percent trips in about six minutes

Answer: The breaker trips on its thermal element after about six minutes

Two more breakers protect people rather than conductors. A GFCI breaker compares the current leaving on the hot conductor with the current returning on the neutral and opens when they differ by a few thousandths of an amp, because the missing current is going somewhere it should not, possibly through a person. An AFCI breaker looks for the electrical signature of arcing in damaged cords and connections. Both carry a test button, and both will trip on faults far too small for the thermal or magnetic element to notice.

Solve

Find it, size it, name it

These three challenges use the same drawing and the same model as the simulator. Each one checks your answer at once.

Challenge: Find the part

The lesson names a part of the panel, such as the main bonding jumper or the neutral bar, and you find it on the drawing or pick it from the list.

Challenge: What does the breaker do?

Three currents with their durations: 24 A on a 20 A circuit for ten minutes, 18 A on a 20 A circuit all day, a 3,000 A fault on the dryer circuit. Decide whether the breaker holds, trips on its thermal element or trips at once.

Challenge: Which bus, which voltage?

Name the voltage a one-pole and a two-pole breaker deliver, and pick the pair of positions that lands on both buses.

One habit matters more than any single answer. A breaker that trips is reporting a problem: an overloaded circuit, a damaged appliance, a fault. Find the cause before resetting it, and never replace a breaker with a larger one to stop a nuisance trip. The breaker rating was chosen for the conductors behind the wall, and those have not changed.

Apply

Where panels show up

Panels are the center of residential and light commercial work: service upgrades when a house adds an EV charger, a heat pump or a hot tub; subpanels for garages and additions; circuit additions during remodels; and the service calls that start with a breaker that keeps tripping. Service electricians read a panel the way a mechanic reads an engine bay, and much of that reading is the balance between the buses and the match between each breaker and its conductors.

The same ideas carry into larger equipment. A commercial 208Y/120 V or 480Y/277 V panelboard has three buses instead of two, and a switchboard or switchgear lineup is the same division of one supply into protected circuits at a larger scale. Learn the residential panel well and the bigger gear reads as more of the same.

If this is the kind of work you want more of, the related openings below are residential and service roles where panel work is routine.

Check your understanding

1. A one-pole breaker sits in position 5 of the example panel. What does it deliver to its circuit?

Answer: 120 V, from bus A to the neutral. Odd positions down the column sit on bus A. A one-pole breaker connects one bus to the circuit, and bus to neutral is 120 V.

2. A two-pole breaker takes positions 3 and 4. Why does it deliver 240 V?

Answer: Adjacent positions land on bus A and bus B, and the two buses are 240 V apart. Positions alternate buses, so two adjacent positions give the breaker both hot conductors, which are the two ends of the 240 V winding.

3. Bus A carries 22 A of 120 V loads and bus B carries 14 A of 120 V loads. What does the service neutral carry?

Answer: 8 A. The two return currents flow in opposite directions on the neutral, so it carries the difference: 22 − 14 = 8 A.

4. A 20 A breaker carries 24 A for ten minutes. What happens?

Answer: It trips on its thermal element after several minutes. 120 percent of the rating is an overload. The thermal element warms and trips after about seven minutes on the lesson's curve, well inside the ten minutes.

5. A conductor fails and about 3,000 A flows on the 30 A dryer circuit. Which element opens the breaker?

Answer: The magnetic element, within about a cycle. A hundred times the rating is a fault. The magnetic element trips in about one cycle, long before the thermal element could warm.

Where this knowledge gets used

Sources and further reading

Lessons are free study material. Finishing one does not certify a skill, count toward a license or replace hands-on training under qualified supervision.