Conductors · Calculator · Intermediate · about 16 minutes
Voltage Drop and Wire Size: Calculator and Lab
Every foot of wire is a little resistor, and a long run spends part of the voltage before the load ever sees it. Take a cable apart, predict what length and wire size do to the drop, then run the calculator on an EV charger, a well pump and a detached garage.
You will learn:
- Why a conductor's resistance grows with length and shrinks with cross-section
- What a circular mil is and how the AWG sizes step
- Why single-phase drop counts the length twice and three-phase counts it root three times
- How to work a drop in volts, percent and watts of heat from one formula
- How to pick the smallest size that holds a run under a chosen percent
- What the simple formula leaves out and why ampacity is a separate check
What this model assumes
- Conductors are pure resistances. The lab ignores reactance, so it understates the drop on long AC runs with large conductors, where real calculators use an effective impedance.
- The resistivity constants are K = 12.9 ohm-circular-mil per foot for copper and 21.2 for aluminum, both at 75 °C. Cooler conductors drop a little less, hotter ones a little more, and the adopted code's conductor tables give per-size figures that differ by a few percent.
- The load draws a steady current that does not change as its voltage sags. Real motors draw more current at lower voltage, so the drop at a motor is a little worse than the figure.
- Single-phase runs count the one-way length twice, once out and once back; balanced three-phase runs count it root three times. The lab does not check ampacity, the current a conductor may carry, which the adopted code's tables decide.
What voltage drop is
A copper conductor is a very good conductor and a very poor insulator, but it is still a resistor. Push current through a hundred feet of it and a few volts are spent along the way as heat, exactly the way Ohm's law says they must be. The voltage that reaches the load is the source voltage minus that loss, and the loss is what electricians call voltage drop. On a short branch circuit it is small enough to ignore. On a run to a detached garage, a well pump at the back of a property or an EV charger at the far end of a parking lot, it decides the wire size.
Two things set a conductor's resistance. The longer it is, the more resistance it has, in direct proportion. The thicker it is, the less resistance it has, in inverse proportion to its cross-section area. Electricians measure that area in circular mils: take the diameter in thousandths of an inch (mils) and square it. A 12 AWG conductor is about 81 mils across, so it has about 6,530 circular mils. Put the two facts together with a constant for the metal, and the resistance of any run comes out of one line of arithmetic.
The current has to get to the load and come back, so a single-phase circuit has two conductors in series as far as the current is concerned, and the run length counts twice. That is the 2 in the formula every electrician carries. In a balanced three-phase circuit the return currents of the three lines partly cancel, and the length counts root three times instead.
A 20 A load at the end of 100 feet of 12 AWG
Given: 120 V circuit, 20 A load; 100 feet one way, 12 AWG copper, 6,530 circular mils; K = 12.9
- Conductor in the circuit: 2 × 100 = 200 feet
- R = 12.9 × 200 ÷ 6,530 = 0.395 Ω
- VD = 20 × 0.395 = 7.9 V, which is 6.6 percent of 120 V
- Heat in the wire: 7.9 × 20 = 158 W
Answer: 112 V at the load; 7.9 V and 158 W are lost in the wire
That lost voltage shows up as problems at the end of the run. A motor on low voltage draws more current to do the same work and runs hotter, and a compressor that is marginal to begin with may hum and trip on start. A resistance heater gives less heat than its nameplate says: heat goes with voltage squared, so 10 percent less voltage is 19 percent less heat. Incandescent lamps dim, some LED drivers flicker or drop out, and an EV charger may throttle or fault. The heat in the wire is also money. The 158 W in the example runs all the time the load does, and it buys nothing.
Take a cable apart
The drawing shows a length of 12-2 nonmetallic sheathed cable, the kind pulled through most houses, cut open at one end. Switch to the exploded view to lift the sheath and the paper off the conductors, and tap any piece, or its name in the list, to learn what it does and how it is marked. The strip under the cable draws copper conductors from 14 to 6 AWG at the same scale, so the circular mils in the formula become something you can see.
Interactive: Inside a 12-2 cable
Two habits come out of the drawing. Read the printed legend before the sheath color: the color follows a maker convention that most of the industry adopted in the early 2000s (white for 14 AWG, yellow for 12, orange for 10, black for 6 and 8), and older cable does not follow it. And notice how fast the sizes grow. Every three gauge numbers the area doubles, so 8 AWG has about two and a half times the copper of 12 AWG, and 6 AWG has four times. That is the lever the calculator pulls.
Before you move the sliders
The formula has three levers: length, current and wire size. Commit to a prediction for two of them before the calculator answers. A wrong guess here is worth more than a right one later, because it tells you which lever you had backwards.
Predict first
You double the one-way length of a run and change nothing else. What happens to the voltage drop?
- It stays the same
- It doubles
- It goes up four times
- It halves
What happens
Drop is current times the resistance of the run, and the resistance grows in step with the length. Twice the wire, twice the drop, and twice the heat. Try it: pick the EV charger in the calculator, note the drop, then double the length slider.
Predict first
You swap 12 AWG for 8 AWG on the same run with the same load. The drop becomes about what share of what it was?
- About the same
- About 80 percent of it
- About 40 percent of it
- About 10 percent of it
What happens
8 AWG has about 2.5 times the circular mils of 12 AWG, so the run has 40 percent of the resistance and the drop falls to about 40 percent of what it was. Try it: hold the length and current still and step the size from 12 AWG to 8 AWG, watching the percent.
Run the calculator
The calculator draws the run between the source and the load and keeps every reading in step with the sliders: the resistance of the run, the drop in volts and in percent, the voltage left at the load and the watts turned into heat along the way. Start from a load you know, then change one thing at a time. The meter under the drawing reads between any two points you put its probes on, so you can measure the drop on one conductor, or the voltage at the load, the way you would on a job.
Interactive: Voltage drop calculator and run
Things worth trying. Pick the well pump and watch 12 AWG lose nearly five percent over 400 feet, then let the button find the size that holds three. Switch the EV charger from copper to aluminum of the same size and watch the percent climb, which is why aluminum runs are sized up. Move the receptacle circuit from 120 V to 240 V and see the volts stay put while the percent halves. Put the red probe on the source hot terminal and the black probe on the load hot terminal: that is the drop on one conductor, half of the total.
Three sizes, one run
Given: 120 V, 20 A, 100 feet one way, copper; 12 AWG: 6,530 cmil. 10 AWG: 10,380 cmil. 8 AWG: 16,510 cmil
- 12 AWG: 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V, 6.6 percent
- 10 AWG: 2 × 12.9 × 20 × 100 ÷ 10,380 = 5.0 V, 4.1 percent
- 8 AWG: 2 × 12.9 × 20 × 100 ÷ 16,510 = 3.1 V, 2.6 percent
Answer: 8 AWG is the first size under 3 percent on this run
| Size | Circular mils | Ohms per 1,000 ft |
|---|---|---|
| 14 AWG | 4,110 | 3.14 |
| 12 AWG | 6,530 | 1.98 |
| 10 AWG | 10,380 | 1.24 |
| 8 AWG | 16,510 | 0.781 |
| 6 AWG | 26,250 | 0.491 |
| 4 AWG | 41,740 | 0.309 |
| 3 AWG | 52,630 | 0.245 |
| 2 AWG | 66,370 | 0.194 |
| 1 AWG | 83,690 | 0.154 |
| 1/0 AWG | 105,530 | 0.122 |
| 2/0 AWG | 133,080 | 0.0969 |
| 3/0 AWG | 167,810 | 0.0769 |
| 4/0 AWG | 211,600 | 0.061 |
Read the table down and the pattern holds all the way: three sizes doubles the circular mils and halves the ohms. Read it against a run and it answers the field question directly. A 12 AWG conductor has 1.98 ohms per thousand feet, so 200 feet of it, out and back, is 0.395 ohms, and 20 A through that is the 7.9 V of the first example.
What the simple formula leaves out
The formula is the one on every electrician's reference card and it is right to within a few percent for most runs. It is worth knowing where the few percent come from, because the manufacturers' calculators and the code tables use slightly different figures and a long feeder can land on a different size.
- Temperature. K = 12.9 is copper at 75 °C. Copper's resistance changes by about 0.4 percent for every degree, so a conductor at 30 °C has about 18 percent less resistance than the figure, and one at 90 °C a little more.
- Reactance. Alternating current in a conductor also sees inductive reactance, which grows with conductor size and spacing. On a 12 AWG branch circuit it is nothing. On a 500 kcmil feeder in a steel raceway it can be larger than the resistance, which is why calculators for big feeders use an effective impedance that depends on the raceway and the power factor.
- The load. The formula takes the current as fixed. A resistance heater draws less current as its voltage sags; a motor draws more. Starting current for a motor is several times its running current, and the drop during the start is what makes a marginal compressor stumble.
- Aluminum. The constant handles the metal, but aluminum terminations need the right connectors, antioxidant where the maker calls for it and the listed torque, none of which a drop calculation checks.
- Ampacity. How much current a conductor may carry is a separate question, answered by the adopted code's ampacity tables and the temperature ratings of the terminations. A conductor sized for voltage drop is usually larger than ampacity alone requires, and the overcurrent device still has to protect it. The lab does not check ampacity.
Size it, find it, predict it
Three challenges on the same engine as the calculator. Each one checks your answer at once and shows the drop behind it.
Challenge: Find the part
The lesson names a part of the cable, such as the bare grounding conductor or the printed legend, and you find it on the drawing or pick it from the list.
Challenge: Pick the smallest size
Three runs with a 3 percent limit: an EV charger at 240 V and 32 A, 120 feet away; a well pump at 240 V and 12 A, 400 feet away; a 120 V receptacle circuit at 16 A, 180 feet away. Pick the smallest copper size that holds the limit and see the drop of every choice.
Challenge: Which way does it move?
Three changes to a run, one at a time: double the length, halve the current, go from 12 AWG to 8 AWG. Say what the drop becomes as a share of what it was.
One habit matters more than any single answer. Work out the percent, then ask what the load will do with the voltage it gets. A lighting circuit at 4 percent is fine; a compressor at 4 percent on a hot day may be a callback. The number is a tool for that judgment.
Where voltage drop shows up
Voltage drop is behind a whole family of service calls: lights that dim when the well pump starts, a shop compressor at the end of a long run that trips its breaker on start and runs fine on a short cord, an EV charger that throttles itself at the far end of a parking lot, a detached garage where every tool seems weak. The fix is rarely a bigger breaker and often a bigger conductor, a shorter route or a higher voltage.
On new work it is a design step. Estimators size long feeders for drop and price the extra copper, project managers and foremen check the runs that changed during construction, and the journeyman pulling the circuit to the pool house is the last person who can catch a run that grew by eighty feet on site. Farms, wells, irrigation, outbuildings, docks, parking lots and EV charging are where the calculation earns its keep.
If this is the kind of work you want more of, the openings below are residential, service and EV charger roles where long runs are part of the day, and the estimator guide covers how the people who size feeders work.
Check your understanding
1. A 20 A load sits at the end of 100 feet of 12 AWG copper on a 120 V circuit. About how much voltage is lost in the run?
Answer: 7.9 V. VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.9 V, about 6.6 percent of 120 V. The run is 200 feet of conductor, out and back.
2. Which single change cuts a run's voltage drop the most?
Answer: Going from 12 AWG to 8 AWG. 8 AWG has about 2.5 times the circular mils of 12 AWG, so the drop falls to about 40 percent of what it was. Halving the current only halves it, and aluminum of the same size raises it.
3. The same 12 AWG run and the same 20 A load, but the circuit is 240 V instead of 120 V. What happens to the drop?
Answer: The volts stay at 7.9 V and the percent halves to 3.3 percent. The drop in volts depends on current, length and wire size, and none of them changed. Against 240 V the same 7.9 V is 3.3 percent, which is why higher voltage carries power farther.
4. What is a circular mil?
Answer: The area of a circle one thousandth of an inch across. Diameter in thousandths of an inch, squared. 12 AWG is about 81 mils across, so about 6,530 circular mils.
5. An electrician sizes a long feeder for 3 percent voltage drop and lands on 6 AWG copper. What still has to be checked?
Answer: That 6 AWG may carry that current under the adopted code's ampacity tables and the termination ratings. Voltage drop is one check. The conductor must also be rated to carry the load current, and that comes from the ampacity tables and termination ratings of the code in force, which the lab does not do.
Where this knowledge gets used
- Residential openings: Detached garages, outbuildings and long runs to pool houses are residential work with a voltage drop check in it.
- EV charger openings: Charger circuits are sized for voltage drop as much as for ampacity, and the runs are getting longer.
- Service and repair openings: Dim lights and a compressor that trips on start at the end of a long run begin as service calls.
- How estimators size and price feeders: What electrical estimators do and how electricians move into the role.
Sources and further reading
Southwire
Voltage Drop CalculatorAn independent calculator used to cross-check the lesson's figures.
United States, NEC conductor sizes. Current tool.
Cerrowire
Voltage Drop CalculatorA second independent calculator for the same cross-check.
United States, NEC conductor sizes. Current tool.
Copper Development Association
Electrical applications: building wire and power qualityConductor properties and the energy lost as heat in building wire.
United States. Current site.
National Fire Protection Association
NFPA 70, National Electrical Code (NEC)The voltage drop informational notes in 210.19 and 215.2 and the places that make a limit mandatory.
United States; adopted by jurisdiction. 2026 edition issued August 2025; the 2023, 2020 and 2017 editions remain in force in many states; each state adopts its own edition and amendments.