Home > Electrical Learning Lab > Three-phase power

Fundamentals · Lesson · Intermediate · about 16 minutes

Three-Phase Power: Waveforms, Wye and Delta

Three-phase power runs the motors, the big buildings and the plants. Watch the three voltages turn below, see where the square root of three comes from, and work out the currents in a wye and a delta connection.

Builds on Transformers.

You will learn:

  • Why three voltages 120 degrees apart add up to zero
  • Phase sequence and what swapping two lines does to a motor
  • Line voltage and phase voltage in wye and delta connections
  • Where the square root of three comes from
  • Line current from kVA for a balanced load
What this model assumes
  • The three voltages are equal in size and exactly 120 degrees apart, and the conductors have no resistance.
  • The load is balanced: each phase carries the same current, so the neutral carries none. Unbalanced loads are a later expansion of this lesson.
  • Voltages and currents are pure sine waves. Harmonics from electronic loads are left out.
  • Powers are computed from the apparent power. Where a power factor is used it is stated.
Understand

Why three phases

A single-phase supply gives one voltage that rises and falls through a cycle. A three-phase supply gives three of them, equal in size and spaced 120 degrees apart: when phase A is at its peak, B is a third of a cycle behind and C a third of a cycle ahead. Utilities generate and transmit power this way, and almost every commercial and industrial building takes its service that way.

The spacing does useful work. Three conductors deliver the power that would take six single-phase conductors, so for the same load the copper is lighter. The power delivered to a balanced load is constant through the cycle instead of pulsing twice per cycle, which is why big motors run smoothly. And a three-phase motor needs no starting capacitor or switch: the rotating field is built into the supply.

There is a fact behind all of it that the simulator shows better than words can: at every instant, the three voltages add up to zero. When one is positive the other two together are equally negative. That is why a balanced load returns no current through the neutral, and it is why a three-phase set of conductors can be drawn as three arrows turning together.

Explore

Watch the three phases turn

Press play and watch the three voltages cycle. The dots on the waveform plot mark the value of each phase at this instant, and the three readings below them always add to zero. Pick a system to change the voltage scale, and switch the sequence from ABC to ACB to see the arrows turn in the other order.

Interactive: Three-phase waveforms and phasors

Three sine waves 120 degrees apart drawn against time beside the same three voltages as turning phasors. Readings show the instantaneous value of each phase and their sum, which is always zero, plus the RMS phase and line voltages for the chosen system (208Y/120, 480Y/277, 240 delta or 480 delta). The phase sequence can be set to ABC or ACB. The simulator runs in your browser with JavaScript turned on.

Phase sequence is the order in which the three voltages reach their peaks. ABC means A peaks, then B, then C. Swap any two line conductors and the order becomes ACB. The voltages are unchanged, every meter reads the same, and a three-phase motor fed this way turns in the opposite direction. That is how motor rotation is corrected on site: swap two leads at the motor or the starter. It is also why a conveyor or a pump can run backwards after a motor change if nobody checks.

The voltages in the plot are RMS values, the ones a meter reads. The peak of each wave is the RMS value times the square root of two, so a 120 V phase peaks at about 170 V and a 277 V phase at about 392 V. The readouts under the plot show the instantaneous values at the frozen instant and the RMS values beside them.

Understand

Line voltage, phase voltage, and where the square root of three comes from

A three-phase source has three windings, on a transformer secondary or a generator. How the three windings are joined decides which voltages are available. In a wye (or star) connection one end of each winding is tied together at a common point, the neutral, and the other ends are the three line conductors. In a delta connection the windings are joined end to end in a triangle, and the line conductors come off the three corners.

Two voltages matter. The phase voltage is the voltage across one winding. The line voltage is the voltage between two line conductors. In a delta they are the same thing, because a line-to-line pair is one winding. In a wye they differ, because the voltage between two lines is the difference between two phase voltages that are 120 degrees apart.

Two 120 V phases, 120 degrees apart

Given: Phase A: 120 V at 0 degrees; Phase B: 120 V at 120 degrees behind

  1. Draw both as arrows from the neutral point, 120 degrees apart
  2. The line-to-line voltage is the arrow from the tip of B to the tip of A
  3. Its length works out to 120 × 1.732, the square root of three, from the geometry of the triangle

Answer: 208 V between lines A and B

V line = √3 × V phase (wye)
Between two lines of a wye system you read the square root of three, about 1.732, times the line-to-neutral voltage.
V line = V phase (delta)
In a delta, each line-to-line pair is one winding.

The square root of three is not a convention anyone chose. It is the length of the third side of a triangle whose two other sides are equal and meet at 120 degrees. The phasor diagram in the simulator shows that triangle: pick any two arrows and the line between their tips is the line voltage.

Common systems and the voltages they offer
SystemConnectionLine to lineLine to neutralWhere you meet it
208Y/120 VWye208 V120 VOffices, retail and small commercial buildings
480Y/277 VWye480 V277 VLarger commercial and industrial buildings, with 277 V lighting
240 V deltaDelta240 V120 V from two legs with a center tap, 208 V from the high legOlder commercial services
480 V deltaDelta480 VNo neutralIndustrial motor loads

The 240 V delta deserves a word. Some of these systems center-tap one winding to supply 120 V loads. The two line conductors at the ends of that winding read 120 V to the center tap. The third line conductor reads about 208 V to the center tap, which is why it is called the high leg. A 120 V load connected to the high leg by mistake sees 208 V and does not last long.

Experiment

Wye and delta under load

The second simulator connects a balanced load to each of the four systems. Move the load in kVA and read the line current, the current in each winding or load element, and the voltage across each. The wye shows line current equal to phase current while the voltages differ by the square root of three; the delta shows the opposite. Power comes out the same either way.

Interactive: Wye and delta connections under load

A three-phase source and a balanced load drawn as a wye or a delta, following the chosen system. A kVA control sets the load, and readings show the line voltage, the phase voltage, the line current, the phase current, the apparent power and the current the same load would draw on single-phase at the same voltage. Each part of the drawing can be tapped for an explanation. The simulator runs in your browser with JavaScript turned on.
S = √3 × V line × I line
Apparent power in volt-amperes from the line quantities. Divide by 1,000 for kVA.
I line = kVA × 1,000 ÷ (√3 × V line)
Line current for a balanced three-phase load. The formula is the same for wye and delta.

A 50 kVA load on 480 V

Given: Balanced load, 50 kVA; 480 V three-phase

  1. I = 50 × 1,000 ÷ (1.732 × 480)
  2. I = 50,000 ÷ 831

Answer: 60 A in each line conductor

The same 50 kVA on single-phase

Given: 50 kVA; 240 V single-phase

  1. I = 50 × 1,000 ÷ 240

Answer: 208 A in each of two conductors, about three and a half times the three-phase line current

That last example is the business case for three phases. The same power needs far smaller conductors, breakers and transformers when it is split over three lines. It is also why the formula sheet an electrician carries has the square root of three on nearly every line of the three-phase section.

In a delta connection the current in each winding is the line current divided by the square root of three, because each line is fed by two windings. Transformer and motor nameplates give line quantities, so when a delta winding is checked the phase current is the smaller number. In a wye the winding current is the line current, and each winding sees only the line-to-neutral voltage.

Solve

Work the numbers

Three challenges, each checked against the same model as the simulators. The first two are quick picks, the third asks for a calculated current.

Challenge: Line or phase?

Given a line-to-neutral or a line-to-line voltage and the connection, pick the other voltage: 120 V phases to 208 V lines, 480 V lines to 277 V phases, and a delta where the two are the same.

Challenge: Find the part

The lesson names a part of the wye connection, such as the neutral point or line conductor B, and you find it on the drawing or pick it from the list.

Challenge: Size the line current

Three balanced loads on named systems: work out the line current in amps from the kVA and the line voltage, within two percent.

A habit that helps: before any three-phase calculation, write down whether the numbers you have are line or phase quantities. Nameplates and panel schedules use line values. Winding ratings and single elements use phase values. Most mistakes in this topic come from mixing the two.

Apply

Where three-phase work takes you

Three-phase systems are the commercial and industrial side of the trade: switchgear and distribution in office buildings, 480Y/277 V lighting and HVAC in warehouses, motor control in plants, and the services that feed all of it. Commercial electricians read 208Y/120 panel schedules daily; industrial electricians size motor feeders and troubleshoot rotation and single-phasing.

The same ideas scale to the next lessons. Transformers change between these systems, and a 480 V delta to 208Y/120 V wye transformer is how a building gets its receptacle and lighting voltage from a 480 V service. Panelboards are built around the phase arrangement, and data centers run everything through three-phase distribution down to the rack.

If this is the work you want, the openings below lean toward commercial and industrial contractors, where three-phase is the daily voltage.

Check your understanding

1. In a 208Y/120 V system, what does a meter read from one line conductor to the neutral?

Answer: 120 V. The Y in 208Y/120 means wye, and 120 V is the line-to-neutral (phase) voltage. 208 V is read between two lines.

2. A wye system has 277 V from each line to the neutral. What is the voltage between two line conductors?

Answer: 480 V. 277 × 1.732 = 480 V. The square root of three comes from two equal voltages 120 degrees apart.

3. A balanced 50 kVA load is fed from a 480 V three-phase system. About what current flows in each line conductor?

Answer: 60 A. I = 50,000 ÷ (1.732 × 480) = 60 A. The same load single-phase at 240 V would draw 208 A.

4. In a delta connection, how does the current in each winding compare with the line current?

Answer: The winding current is the line current divided by the square root of three. Each line in a delta is fed by two windings, so the winding (phase) current is the line current divided by 1.732.

5. You swap two of the three line conductors feeding a three-phase motor. What changes?

Answer: The motor turns the other way. Swapping two lines reverses the phase sequence from ABC to ACB. The voltages and currents are unchanged, and the rotating field, with the motor, turns the other way.

Where this knowledge gets used

  • Commercial openings: Commercial electricians work on 208Y/120 and 480Y/277 V systems every day, from services to panel schedules.
  • Industrial openings: Industrial electricians size motor feeders, correct rotation and troubleshoot three-phase equipment.
  • Working as a journeyman: What journeyman electricians are expected to know and how the role grows.

Sources and further reading

  • Tony R. Kuphaldt (ibiblio)

    Lessons In Electric Circuits (six volumes)

    Polyphase systems, Volume II chapter 10.

    Global, physics and circuit theory; US examples. Volume editions dated per volume (DC 5th, AC 6th).

  • Schneider Electric

    Electrical Installation Guide (wiki)

    Low-voltage distribution systems and connections.

    IEC and international; not the US NEC. Living wiki; chapters dated per page (IEC 60364-4-42 2024 update noted on the main page).

  • National Fire Protection Association

    NFPA 70, National Electrical Code (NEC)

    High-leg marking and phase arrangement, 110.15 and 408.3.

    United States; adopted by jurisdiction. 2026 edition issued August 2025; the 2023, 2020 and 2017 editions remain in force in many states; each state adopts its own edition and amendments.

Lessons are free study material. Finishing one does not certify a skill, count toward a license or replace hands-on training under qualified supervision.