Residential · Troubleshooting workshop · Intermediate · about 45 minutes
Explore the Electrical System of a House
Every house runs on the same few ideas: a service, a panel, branch circuits, and devices wired in boxes. Walk through a training house in 3D, take the walls down to see where the cables run, put a meter on any device, then find a real fault and repair it the way the work is done.
You will learn:
- How power reaches a light: service, main breaker, bus, branch breaker, cable, box, switch and back on the neutral
- How a house is divided into branch circuits, and how to trace one
- What a meter reads across a switch, and why a GFCI also protects the outlets wired from it
- How to find a fault by predicting what each cause would read, then measuring
- Why the absence of voltage is tested with a meter proven on a live source before and after
- How the neutral, the equipment grounding conductor, the bonding jumper and the ground rods each do their own job
- How receptacle spacing is measured along the floor line, and why more outlets do not add amps
What this model assumes
- The house is a teaching model with six branch circuits, so each one stays easy to follow. A real dwelling has more: at least two 20 A small-appliance circuits for the kitchen counters, a laundry circuit, and circuits for the range, dryer, water heater and heating, among others. The house also has fewer outlets and lights than a dwelling needs: no refrigerator, laundry or outdoor receptacle and no lights at the outside doors.
- The service shows the meter, an outdoor disconnect, the main breaker and two ground rods. A new service also calls for a surge protective device and an intersystem bonding termination and, where they exist, a concrete-encased electrode and water pipe bonding; none of those are drawn. The mast and service drop are drawn for teaching, with heights left to the utility's rules.
- Loads are resistive. A lamp or a coffee maker is the resistance that draws its rated watts at 120 V; there is no reactance, no motor and no electronic power supply in the model.
- Each conductor has the copper resistance of its size and length, the figure from the voltage drop lesson. Contacts, splices and bus stabs are a few thousandths of an ohm.
- The meter is ideal. A real digital meter can show a few volts on a disconnected wire that runs in the same cable as a wire carrying power; the model reads zero there.
- A breaker opens at once on a short circuit. The time a breaker takes to trip on an overload is not modeled here, and an AFCI breaker conducts like a standard one: the model does not simulate arcs.
- A GFCI opens when the current on its hot and neutral differ by more than about 5 mA, the figure from the protection lesson.
- The walls, framing and heights are typical of a modest house: a training model, drawn for learning, and no design for construction. There is no attic access drawn; cable across joist tops near an access opening or a walkable attic floor needs protection a drawing of this size leaves out.
- In the outlet job, spacing is measured on the living room's walls only. Fireplaces, fixed cabinets, fixed panels, room dividers and floor outlets, which change the measure in a real room, are left out. Each wall space is measured on its own, the common reading.
- The lamp's 6 ft cord in the outlet job is this model's input. The code does not name a cord length, and a real cord also has to climb from the floor to the outlet.
- Outlets added in the job go on the end of circuit 1 in 14 AWG, on the same breaker. Each cable length is an estimate, a straight line from the box before it plus 3 ft for the drops and rises, and the cable is not drawn.
- The furniture is scenery from public 3D datasets. It does not change the spacing measure, and no reading comes from it.
How power moves through a house
The utility's transformer feeds a house two 120 V legs and a grounded neutral. From either leg to the neutral is 120 V; from leg to leg is 240 V. The service conductors pass the meter and an outdoor disconnect, come through the wall a short way from the panel, and land on the main breaker, the service disconnect for the whole house, inside the load center.
In the load center the main breaker feeds two bus bars, one per leg. Each branch breaker clips onto one bus, and each breaker starts a branch circuit: a cable that leaves the panel, runs through the walls and the attic to boxes, and feeds the receptacles, switches and lights on that circuit. Breakers alternate legs down the panel, so a 120 V circuit takes one leg and a 240 V circuit takes both.
Inside a cable there are three conductors. The black hot carries current out to the loads. The white neutral carries it back to the neutral bar. The bare equipment grounding conductor carries nothing at all in normal use; it bonds every box and device to the panel so a hot that touches metal makes a short path back that trips the breaker.
A switch goes in the hot. With the switch open, the light has no voltage on it at all, and its neutral is spliced straight through the switch box. A receptacle has two brass screws for the hot and two silver screws for the neutral, joined by break-off tabs, so a cable from the second pair carries power on to the next outlet on the circuit.
Interactive: Trace the circuits on the plan
Walk the training house
The training house is one story, 40 ft by 28 ft, with a bedroom, a bathroom, a laundry, a hallway, a living room and a kitchen, and a 22 ft by 24 ft garage. The load center hangs on the garage side of the wall the garage shares with the house. The meter is on the garage's front wall, just outside, so the service conductors run only a few feet inside. Open it in 3D and orbit around it, or walk through the rooms at eye height.
The walls come down four ways. Cutaway cuts them low so you can look into every room. See-through keeps them as glass, with the studs and cables visible behind. Framing strips the drywall to show the studs 16 in on center, the plates and the headers over each door and window, with the cables running through them. Walls puts the finished house back.
Interactive: The training house in 3D
- Show the lighting circuit on its own and follow its cable from breaker 2 to the junction box in the hallway ceiling, then on to each of its four switch boxes.
- Switch off the bedroom breaker and see which lights and outlets go dark.
- Take the walls down to Framing in the garage and find the conduit that steps out onto the furred section of wall.
- Turn on Voltage and watch which cables go dead when a breaker opens.
Predict before you measure
Commit to an answer first. Then open the house and let the meter answer.
Predict first
The living room light is off at its switch. You put the meter's probes on the switch's two screws. What does it read?
- 0 V, because the switch is off
- About 120 V
- About 240 V
What happens
About 120 V. One screw is connected to the hot; the other is connected through the lamp to the neutral, which sits near 0 V. The open switch holds back the whole 120 V, so all of it appears across the switch. Try it: In the Experiment stage, put the probes on the living room switch, read it, then switch the light on and read again.
Predict first
The kitchen's second outlet, by the corner, is wired from the GFCI's LOAD terminals. You press TEST on the GFCI. What happens to the coffee maker on the corner outlet?
- Nothing; it is a separate outlet
- It goes off too
- The kitchen breaker trips
What happens
It goes off too. The GFCI opens its LOAD terminals, and everything wired from them loses power with it. That is how one GFCI protects a whole string of outlets. Try it: Press TEST on the kitchen GFCI in the house, then RESET.
Predict first
A lamp plugged into an outlet does not light. Hot to neutral reads 0 V there. What does hot to ground read if the neutral is broken somewhere upstream?
- 0 V
- About 120 V
- About 60 V
What happens
About 120 V. The hot is still connected all the way back to the breaker, so it reads 120 V to the ground. The neutral beyond the break is pulled up to the hot through the lamp, which is why hot to neutral reads nothing. Try it: Measure hot to ground at the dead outlet in the Solve stage.
Test it with the meter
Pick a device in the house and its terminals appear in a list beside the meter. Tap one for the red probe and another for the black, and the meter shows the voltage between them, solved from the circuit as it stands. A live receptacle is read at its face, with the probes in the slots and the plate on; a switch has only its screws, and a receptacle comes out of its box to be read on its screws only after its breaker is off. The meter also reads ohms, between two points with the power off and anything plugged in there unplugged, because the meter reads through a load as readily as through a fault, and amps with a clamp around one wire. On real work a clamp goes on a single conductor only with the cover off, by a qualified person; for something plugged in, a line splitter at the plug keeps the box closed.
Across the living room switch with the light off, the meter reads about 120 V; switch the light on and it falls to about 0 V. Across the light itself the readings swap. That is a meter's view of a series circuit: the open contact holds back the whole supply, and the closed contact drops almost none of it.
Press TEST on the kitchen GFCI and it clicks off, and the coffee maker on the corner outlet goes dark with it. The TEST button sends a little current around the device's sensing coil, so the current going out on the hot no longer matches the current coming back on the neutral. Press RESET and both outlets come back.
Challenge: A switch and a GFCI, measured
In the training house, read across a light switch with its light off and again with it on, then press TEST on the kitchen GFCI and reset it. The house checks your readings against the circuit.
Find the fault
A homeowner calls: the lamp plugged into the outlet by the bed will not come on, the bedroom light works, and a phone charger works in the outlet by the window. Before you measure anything, list what could cause that: a burned-out lamp, a broken hot or a broken neutral between two of the outlets, a tripped breaker, a broken ground wire. Then work out what each cause would read.
Some causes fall away on the homeowner's word alone. A tripped bedroom breaker would also darken the bedroom light. A broken ground wire carries no current in normal use, so it cannot stop a lamp. A break between the first and second outlets would stop the phone charger too. What is left: the lamp, an open hot, or an open neutral beyond the second outlet.
Hot to neutral at the dead outlet reads 0 V with an open hot or an open neutral; a burned-out lamp leaves it at a full 120 V. Hot to ground then tells the two opens apart: about 120 V with an open neutral, because the hot is still connected, and about 0 V with an open hot. In the house, the diagnosis counts only when your own readings rule out every other cause on the list.
Challenge: What is wrong with the bedside lamp?
A fault is hidden in the training house. Take readings until they prove what it is and where, then name the cause. The house simulates every cause on the list against every reading you took, and asks for one more reading if yours still fit two causes.
Readings at the outlet by the bed, with the lamp plugged in
Given: Hot to neutral: 0 V; Hot to ground: 120 V; Neutral to ground: 120 V
- The hot reaches the outlet, because hot to ground is 120 V.
- The neutral is not connected back to the panel, because it sits at 120 V to ground: the lamp's filament ties it to the hot.
- With no path home on the neutral, no current flows and the lamp stays dark.
Answer: An open neutral between the second outlet and the outlet by the bed
Repair it safely
The repair is small: the white wire to the outlet by the bed was pushed into a backstab hole on the second outlet and worked loose, so it moves to the silver screw and is tightened to the torque marked on the device, and the other backstabbed connections on that device get checked while it is out. The order around it is what matters, and the house checks it step by step from the state of the circuit.
- Switch off the breaker that feeds the box, then lock it off and tag it so nobody can switch it back on. A tripped GFCI also leaves a box dead, but anyone can reset it, so it does not count.
- Check your meter on an outlet you know is live, on the same voltage setting, with the power off at the box you will work in.
- Test the box with the power off: hot to neutral, hot to ground and neutral to ground, all near 0 V.
- Check the meter on the live outlet again.
- Make the repair.
- Take your lock off, switch the breaker back on and measure hot to neutral at the outlet that had the problem.
Testing a known live outlet before and after the dead test proves the meter worked the whole time; a meter with a dead battery or a broken lead reads 0 V everywhere, and that reading would lie. NFPA 70E's process for verifying an electrically safe work condition works the same way, and it is done by a qualified person. A non-contact tester is a handy first check of which wires are live, but it never proves a circuit dead: only a meter tested on a known source does that. In the house, if the power comes back on before the repair, the testing starts over.
Challenge: Repair the bedroom outlet
In the training house: switch the right breaker off, prove the meter on a live outlet, test the box with the power off three ways, prove the meter again, make the repair, restore power and check the outlet. The house will not let you put a hand in a box that is fed or untested.
The garage has a second job. Its EMT runs along the north wall and has to step 6 in out onto a furred section whose face starts 26 in past the last coupling. That is the two-bend offset from the conduit lesson turned on its side: with Klein Tools' 30° row, 1-1/2 in of shrink puts MARK A at 27-1/2 in and MARK B 12 in back at 15-1/2 in. Bend it in the bending lab and the piece comes back to the house, where its own centerline is checked against the wall.
Challenge: Bend the garage offset
Open the bending lab from the house with the garage job set up: 1/2 in EMT on a Klein Tools bender, 30 degrees, a 6 in step 26 in from the coupling. The house sets your piece on the wall and checks whether it clears the furring's corner, lies on its face and runs level.
Lay out the outlets
The living room in this house has three outlets, fewer than a dwelling needs, on purpose, so its circuit stays easy to follow. The rule they fall short of is simple to measure. Walk the floor line of a wall, around its corners, and no point on it may be more than 6 ft from an outlet. A doorway or a wide opening ends one wall space and starts the next. A window does not, because the wall carries on under it.
The purpose is reach. A lamp or an appliance with a flexible cord can sit anywhere along a wall and still get to an outlet, so nobody needs an extension cord to use the room. Two outlets can be up to 12 ft apart, each reaching 6 ft toward the other. A common way to lay a room out from nothing is 6 ft from each opening and then every 12 ft. The furniture does not enter into it: the measure belongs to the wall.
As built, this room has 20 ft of floor line out of reach. In the job you stand a lamp with a 6 ft cord anywhere along the walls and see where it falls short, then add outlets until no red is left. Keeping the three it has, the room needs five more. Laid out from nothing, the same walls take six in all. The television and the table lamp stay dark until an outlet you add reaches them.
Challenge: Lay out the living room's outlets
In the training house, move a lamp with a 6 ft cord along the living room's walls and add outlets until every point on the floor line is within 6 ft of one. The floor line shows green within reach and red out of reach, measured by wall space, and everything plugged in is solved by the house's circuit engine.
More outlets do not add amps. Every outlet you add goes on the same 15 A circuit, so they all share its breaker. With the lamps and the television on, the breaker reads about 2 A. Plug in a 1500 W space heater and it reads about 14 A. Plug in a second and it reads about 25 A, an overload. A breaker does not open the moment it is overloaded. It heats up first, so an overload can run for a while: the trip curve in the panel lesson, an approximation, puts this much at about 2 minutes. This house does not model that time, so its breaker stays on and tells you the overload is there.
Space heaters are what really trip breakers in a house, and they start fires when they are used carelessly. NFPA and the Consumer Product Safety Commission both say to keep a heater at least 3 ft from anything that can burn and to plug it straight into the wall, with no extension cord or power strip. NFPA adds a solid, flat floor, out of foot traffic and never blocking an exit. Both heaters in the job stand where those distances hold.
Check your understanding
1. A light is switched off. What does a meter read across the switch's two screws?
Answer: About 120 V. About 120 V. One screw is on the hot, the other reaches the neutral through the lamp, and the open contact holds back the whole supply.
2. A second outlet is wired from a GFCI receptacle's LOAD terminals. You press TEST on the GFCI. What happens at the second outlet?
Answer: It loses power too. It loses power too. The GFCI opens its LOAD terminals, so every outlet wired from them goes off with it.
3. With a lamp plugged in at a dead outlet, hot to neutral reads 0 V, hot to ground reads 120 V and neutral to ground reads 120 V. What is the likely cause?
Answer: An open neutral upstream. An open neutral. The hot still reaches the outlet, and the broken neutral is pulled up to the hot through the lamp, so it reads 120 V to ground.
4. Why do you test your meter on a known live outlet before and after testing a circuit with the power off?
Answer: To prove the meter worked during the test. A dead battery or a broken lead reads 0 V everywhere. Proving the meter on a live source before and after shows the 0 V reading in between was real.
5. Where are the neutral and the equipment grounding conductor joined in a house's electrical system?
Answer: At the service, by the main bonding jumper. They meet only at the service, through the main bonding jumper. Everywhere else they stay apart so normal current returns on the neutral alone.
6. Along one wall with no openings, how far apart can two outlets be so that no point on the floor line is more than 6 ft from one of them?
Answer: 12 ft. 12 ft. Each outlet reaches 6 ft along the floor line, so the two reaches meet in the middle.
7. A 15 A living room circuit has a 1500 W heater on it. You add an outlet to the same circuit and plug in a second 1500 W heater. What does the breaker see?
Answer: About 25 A, an overload that can run for a while before it opens. About 25 A, 12.5 A for each heater. More outlets do not add amps, and a breaker heats up before it opens, so an overload can run for a while.
Where this knowledge gets used
- Residential openings: Wiring houses, from rough-in through trim-out and service changes, is everyday residential work.
- Service and repair openings: Finding faults like an open neutral and fixing them safely is the core of service work.
- Starting as an electrician apprentice: What apprentices learn first and how the role grows.
Sources and further reading
National Fire Protection Association
NFPA 70, National Electrical Code (NEC)Switches in the hot, the grounded conductor at switch locations, GFCI and AFCI locations, the required branch circuits, the service disconnect's location and the outdoor emergency disconnect, box fill, bonding steel boxes, ground rods and ground clamps, receptacle spacing and the limit on one cord-and-plug load, cited by number for the reader to check.
United States; adopted by jurisdiction. 2026 edition issued August 2025; the 2023, 2020 and 2017 editions remain in force in many states; each state adopts its own edition and amendments.
National Fire Protection Association
NFPA 70E, Standard for Electrical Safety in the WorkplaceVerifying an electrically safe work condition with a test instrument checked on a known source before and after the test.
United States. 2024 edition current.
US Occupational Safety and Health Administration
29 CFR 1910.333, Selection and use of work practicesDe-energizing and verifying circuits before work, and who may work near energized parts.
United States, general industry. Current CFR text as published by OSHA.
UL Standards and Engagement
UL 943, Standard for Ground-Fault Circuit-InterruptersThe GFCI's trip level of a few milliamps, used by the house's GFCI model.
United States and Canada. Current edition as listed by UL.
Fluke
Digital multimeter basics and troubleshootingHow a multimeter measures volts, ohms and amps, and why ohms are read with the power off.
Global. Current article.
Tony R. Kuphaldt (ibiblio)
Lessons In Electric Circuits (six volumes)Series circuits, why an open switch drops the supply voltage, and how loads and conductors are modeled as resistance.
Global, physics and circuit theory; US examples. Volume editions dated per volume (DC 5th, AC 6th).
Schneider Electric
QO130M200PC load center, product pageThe load center named in the house, the same Square D product modeled in the 3D panel lesson.
United States. Product page as read on the verification date.
Klein Tools
Conduit Bender Guide (Conduit Bending Basics)The offset table row and the bending method behind the garage conduit job.
United States, EMT and rigid conduit hand benders. 12-page PDF, March 2012.
Mike Holt Enterprises
Understanding the 2023 NEC, Volume 1: 210.52, Dwelling Unit Receptacle Outlet RequirementsThe floor-line measure and what counts as a wall space in the outlet job, against 2023 numbering.
United States; adopted by jurisdiction. 2023 NEC edition.
Electrical Contractor magazine
Article 210, Branch Circuits (Code in Focus)Measuring to an outlet in the same wall space, and the floor lamp on a 6 ft cord as the way to picture the rule. An older article, used for the reading and the picture.
United States. May 15, 2002, on the 2002 edition; the publisher marks it as an older article.
Mike Holt's Forum
210.52(A)(1) spacing issueThat an outlet across a doorway is argued over in the words, and that working electricians read a door as ending the wall space.
United States. Thread from April 2010; opinions, no official interpretation.
EC&M
Stumped by the Code? June 2011 (Mike Holt)The purpose of the spacing rule: fewer extension cords.
United States. June 21, 2011.
EC&M
Code Q&A: Cord- and Plug-Connected Equipment (Mike Holt)The 80 percent limit on one cord-and-plug load, and that laboratories list portable equipment up to the full rating.
United States. September 6, 2012, on the edition then current; check the numbering against your own.
National Fire Protection Association
Electric Portable Space Heater Safety (tip sheet)The space heater guidance in the outlet job: 3 ft from anything that can burn, straight into the wall, a solid flat floor, out of foot traffic, never blocking an exit.
United States. NFPA 2018.
U.S. Consumer Product Safety Commission
Keep Warm and Safe This Winter: Tips for Using Generators, Furnaces and Space HeatersThe 3 ft and the wall outlet with no extension cord or power strip.
United States. January 23, 2026.
U.S. Consumer Product Safety Commission
Reducing Fire Hazards for Portable Electric Heaters (Publication 098)The 3 ft on every side of a heater, and a stable, level surface.
United States. Pub. 098, 2013.
Amazon.com and UC Berkeley
Amazon Berkeley Objects (ABO) datasetThe furniture and lamps, adapted as scenery. Credited below.
Global. Dataset as published with the CVPR 2022 paper; read through CodePawl's web-ready copy.
NVIDIA
SimReady AssetsThe television, adapted as scenery. Credited below.
Global. Dataset as published on Hugging Face; read through CodePawl's web-ready copy.
CodePawl
Web-ready GLB copies of ABO and SimReadyThe web-ready copies the props were cut from.
Global. As published on Hugging Face.
Furniture in this lesson is adapted from the Amazon Berkeley Objects dataset. Credit for the data, including the 3D models, goes to Amazon.com. The dataset was built by Matthieu Guillaumin, Thomas Dideriksen, Kenan Deng, Himanshu Arora, Arnab Dhua, Xi (Brian) Zhang and Tomas Yago-Vicente of Amazon.com, and Jasmine Collins, Shubham Goel and Jitendra Malik of UC Berkeley. The television is adapted from NVIDIA SimReady Assets. Both are licensed under CC BY 4.0 and provided as is, with no warranty. Web-ready versions were prepared by CodePawl (ABO, SimReady). We changed the files: simpler shapes, smaller textures, new file names, names and metadata removed. Amazon, NVIDIA and CodePawl did not make this lesson and do not endorse it or Electrician Jobs Near Me.
Lessons are free study material. Finishing one does not certify a skill, count toward a license or replace hands-on training under qualified supervision.