Home > Electrical Learning Lab > Grounding and bonding

Grounding · Equipment explorer · Intermediate · about 18 minutes

Grounding, Bonding and Subpanels: Inside the Panel

A ground fault only trips a breaker because somebody built it a path home. Take a service panel and a subpanel apart below, then fault an appliance and watch where the current goes, with and without the pieces that make the path.

Builds on Electrical panels, Split-phase service.

You will learn:

  • The difference between grounding and bonding, and what each one is for
  • Why the earth cannot clear a fault and the bonding jumper can
  • The effective ground-fault current path from an appliance case back to the transformer
  • What touch voltage is and how much current a person becomes
  • Why a subpanel keeps its neutrals and grounds apart and what happens when it does not
What this model assumes
  • Loads are resistive and the service is modeled as two 120 V sources in series. Conductors have fixed resistances: 0.02 ohm per service conductor, 0.08 ohm per branch-circuit conductor, 0.05 ohm per feeder conductor, and 0.001 ohm for a bonding connection.
  • The grounding electrodes are 25 ohms to earth each, at the utility pole and at the service, and the earth between them is a perfect conductor. Real electrode resistance runs from a few ohms to several hundred.
  • A person touching a case is a 1,000 ohm resistor from the case to the earth, a common planning figure for wet skin. Readings in a fault are the instant before the breaker opens.
  • Breakers follow the panel lesson's curve: about one cycle at ten times their rating. GFCI protection is left out here; it has its own lesson.
Understand

Grounding and bonding are two different jobs

Electricians say grounding for two things that behave very differently, and a lot of confusion on the job comes from blurring them. Grounding is connecting the electrical system to the earth: the ground rod, the water pipe, the rebar in the footing, and the grounding electrode conductor that ties the panel to them. Bonding is connecting the metal parts of the installation to each other and to the grounded conductor, the neutral, so that if a hot conductor ever touches one of them, the current has a fat, short path back to the transformer.

Grounding to the earth limits the voltage the system can be pushed to by lightning and by contact with higher-voltage lines, and it holds the metal parts near the voltage of the ground people stand on. What it cannot do is clear a fault. The earth is a poor conductor path. A single ground rod is allowed to measure 25 ohms, and the utility's rod at the pole adds its own. Put 120 V across 50 ohms and you get 2.4 A, which a 20 A breaker will carry all day.

Why the earth cannot clear a fault

Given: A hot conductor touches a metal case that is connected only to a ground rod; Service rod 25 ohms, utility rod 25 ohms, 120 V

  1. Total path through the earth: 25 + 25 = 50 ohms
  2. Current: 120 ÷ 50 = 2.4 A
  3. The branch breaker is rated 20 A

Answer: About 2.4 A flows, the breaker holds, and the case stays at line voltage until something changes

Bonding is what clears the fault. The bare or green equipment grounding conductor that runs with every circuit connects the metal case of the appliance to the ground bar in the panel. At the service, one deliberate connection, the main bonding jumper, ties that ground bar and the enclosure to the neutral bar. From there the service neutral runs straight back to the transformer. That chain is the effective ground-fault current path: a few hundredths of an ohm instead of fifty, so a fault to a case pulls hundreds of amps for the cycle it takes the breaker's magnetic element to notice.

Explore

Inside the service panel and the subpanel

The drawing shows a service panel feeding a subpanel in a detached garage, both with their dead fronts off. Switch to the exploded view to pull the pieces apart, and tap any piece, or its name in the list, to read what it does and where it goes wrong. Two pieces decide the whole lesson: the main bonding jumper, which exists once and only at the service, and the subpanel's neutral bar, which sits on insulators so that no second bond can form.

Interactive: Service panel and subpanel

An exploded view of a service panel and a subpanel side by side: the neutral bar with the incoming service neutral, the main bonding jumper, the ground bar, the grounding electrode conductor and ground rod, the two-pole feeder breaker, the four-wire feeder, the subpanel's isolated neutral bar, its bonded ground bar, the bonding screw left out, and a branch circuit's grounding conductor out to an appliance. Each piece is named and explained. The simulator runs in your browser with JavaScript turned on.

Follow the feeder across. Two hot conductors leave a two-pole breaker and land on the subpanel's lugs. The neutral leaves the service neutral bar and lands on the subpanel's neutral bar, which is mounted on insulating standoffs. The equipment grounding conductor leaves the ground bar and lands on the subpanel's ground bar, which is bolted straight to the metal enclosure. Four conductors, two bars, no connection between the bars: that is a subpanel wired the way the rest of this lesson explains.

Predict

Call it before you fault it

Two situations the fault path lab below can show. Commit to an answer before you run them.

Predict first

The hot conductor touches the metal case of a washing machine on an old two-wire circuit with no grounding conductor. The washer keeps running. What does the breaker do?

  1. Trips at once
  2. Trips after a few minutes
  3. Holds, and the case sits at line voltage
What happens

With no grounding conductor the fault has nowhere to go. The breaker sees only the washer's normal current, and the case waits at about 120 V for someone to touch it. Try it: pick Fault, no ground wire in the lab and put the meter between the case and the earth.

Predict first

A subpanel's neutral bar is bonded to its enclosure by mistake, and a 1,500 W heater runs from that subpanel. What flows on the feeder's grounding conductor?

  1. Nothing, it only carries fault current
  2. About half of the heater's return current
  3. The full heater current
What happens

The neutral and the grounding conductor are now two parallel paths back to the service, so the return current splits between them, about half each when the conductors match. Try it: pick Subpanel, bonded and read the feeder grounding conductor.

Experiment

Follow the fault

The lab runs the same service as the split-phase lesson with an appliance on a 20 A circuit. Pick a situation, switch the grounding conductor, the bonding jumper and a person touching the case on and off, and read what flows where. The conductors that carry the fault light up, and the meter reads between any two probe points, including the appliance case and the earth.

Interactive: The fault path laboratory

A transformer, a service panel with its neutral bar, ground bar and bonding jumper, a grounding electrode, a 20 A circuit to an appliance with a metal case, and a person on a damp floor. Situations: normal operation, a hot-to-case fault with a grounding conductor, the same fault without one, the same fault with a person touching the case, a missing bonding jumper, and a subpanel wired right and wired wrong. Readings show the fault current, the current on the grounding conductor, through the bonding jumper and into the earth, the case voltage to earth, the current through the person and what the breaker does. The simulator runs in your browser with JavaScript turned on.

A fault with a grounding conductor

Given: Hot to case on a 20 A circuit; Path: service hot 0.02, branch hot 0.08, the fault 0.01, grounding conductor 0.08, bonding jumper 0.001, service neutral 0.02 ohm

  1. Total: about 0.21 ohm
  2. Current: 120 ÷ 0.21 is close to 570 A
  3. 570 ÷ 20 = 28 times the rating, far above the magnetic pickup

Answer: About 570 A flows and the breaker opens in about one cycle

A person as the path

Given: The same fault on a circuit with no grounding conductor; A person touches the case while standing on a damp floor, 1,000 ohms

  1. Current: 120 ÷ 1,000 = 0.12 A
  2. 0.12 A = 120 mA

Answer: About 120 mA through the person, far into the range that stops a heart, while the breaker holds

What the model shows for each situation
SituationFault currentThe breakerCase to earth
Normal operation0 AHolds0 V
Fault, grounded caseAbout 570 AOpens in about one cycleAbout 50 V for that cycle
Fault, no grounding conductor0 AHoldsAbout 120 V
Fault, missing bonding jumperAbout 2.4 AHoldsAbout 60 V
Subpanel bonded by mistakeNo faultHolds0 V, with about 5.6 A on the feeder grounding conductor

Things worth trying. Run the grounded fault and watch the case voltage: it rises to about 50 V for the one cycle the fault lasts, because 570 A through the grounding conductor's 0.08 ohm is a real voltage drop. Then remove the bonding jumper and leave the grounding conductor in place: the case is connected to the ground bar and the ground bar to the earth, and the current still has to come home through two ground rods, so it falls to about 2.4 A and the breaker holds. Last, put the probes from the neutral bar to the ground bar in that situation and read more than 100 V between two bars that normally sit at the same potential.

Understand

Why a subpanel keeps neutrals and grounds apart

The neutral carries current every second a 120 V load runs. The equipment grounding conductor is meant to carry current only during a fault. Bond the two together in a second place, at a subpanel, and the grounding conductor becomes a second neutral: part of every load's return current flows on it, on the metal enclosure, on the conduit, on the water pipe, on anything else bonded along the way. The trade calls that objectionable current, and it is why the bond exists once, at the service, and nowhere downstream.

The lab's two subpanel situations show it. Wired right, with a four-wire feeder and an isolated neutral bar, the feeder's grounding conductor carries nothing while the heater runs. Bond the subpanel's neutral bar to its enclosure and the same heater's return current splits: about half stays on the feeder neutral and about half comes back on the grounding conductor and the metal parts. Nothing trips, nothing looks wrong, and every metal surface between the two panels now carries current.

  • Service panel: neutral bar bonded to the enclosure by the main bonding jumper; the grounding electrode conductor lands here; grounds and neutrals may share this bar.
  • Subpanel: neutral bar isolated on standoffs; a separate ground bar bonded to the enclosure; the bonding screw stays out; neutrals on the neutral bar, grounding conductors on the ground bar, never mixed.
  • Feeder between them: two hots, a neutral and an equipment grounding conductor. A detached building also gets its own grounding electrode, connected to the subpanel's ground bar, never to its neutral bar.
Solve

Trace it, land it

Three challenges on the same drawings and the same model as the lab. Each one checks your answer at once.

Challenge: Find the part

The lesson names a part of the two panels, such as the main bonding jumper or the subpanel's neutral bar, and you find it on the drawing or pick it from the list.

Challenge: Trace the fault current

A hot conductor has touched a grounded appliance case. Build the path the current takes back to the transformer, one hop at a time, from the choices offered at each step.

Challenge: Land the conductors

Five conductors arrive at a subpanel: the feeder neutral, the feeder grounding conductor, a branch neutral, a branch grounding conductor and the green bonding screw. Put each one where it belongs.

One habit matters more than any single answer. When a panel does not make sense, find the main bonding jumper first. If it is at the service and nowhere else, the fault path is probably right and the rest is housekeeping. If it is missing, or if there is a second one at a subpanel, the installation can run for years looking fine while a fault waits to find a person instead of a breaker.

Apply

Where grounding and bonding decide the job

Service upgrades, subpanels for garages and additions, hot tubs, EV chargers and generator connections all come down to the same questions: where is the bonding jumper, does every circuit carry a grounding conductor, does the feeder have four wires, and does the detached building have its own electrode. Inspectors look for those four things first, and an electrician who can explain the fault path in plain words walks through inspections.

Service and repair work meets the other side of it: the old two-wire circuit with a three-prong receptacle, the subpanel someone bonded because the lights flickered, the ground rod clamp corroded through, the water heater case that tingles. Each one is a missing or extra piece of the path this lesson draws, and the meter work that finds them is for qualified people with the right equipment.

The same ideas scale up. Commercial services bond at the service and separately derived systems bond at the transformer, data centers bond every rack and raised-floor pedestal into one grid, and the data center lesson shows why that grid matters. If this is the work you want more of, the openings below are residential and service roles where panels and subpanels are everyday work.

Check your understanding

1. The hot conductor touches the metal case of an appliance that has a grounding conductor back to the panel. Why does the breaker open?

Answer: The grounding conductor and the bonding jumper give the fault a low-resistance path back to the transformer, so hundreds of amps flow. The path through the grounding conductor, the bonding jumper and the service neutral is a fraction of an ohm, so the fault current is far above the breaker's magnetic pickup.

2. Why does a subpanel keep its neutral bar isolated from the enclosure?

Answer: Because a second neutral-to-ground bond would put normal neutral current on the grounding conductor and the metal parts. A second bond makes the grounding conductor a parallel neutral. Current then flows on enclosures, conduit and pipes every time a load runs.

3. The same hot-to-case fault happens on a circuit with no grounding conductor. What does the model show?

Answer: Nothing opens and the case sits near 120 V. With no path back to the source there is no fault current to see. The case waits at line voltage until a person or a damp floor provides the path.

4. Two 25 ohm ground rods are the only path for a fault on a 120 V circuit. About how much current flows?

Answer: About 2.4 A. 120 V across 50 ohms is 2.4 A, far below a 20 A breaker's rating. The earth limits the voltage on metal parts but cannot clear a fault.

5. How many conductors does a feeder to a detached garage subpanel carry in the lesson's drawing?

Answer: Four: two hots, a neutral and an equipment grounding conductor. Two hots, a neutral and an equipment grounding conductor. The neutral lands on the isolated neutral bar and the grounding conductor on the ground bar bonded to the enclosure.

Where this knowledge gets used

  • Residential openings: Service upgrades, subpanels and detached-building feeders are everyday residential work.
  • Service and repair openings: Service electricians find the missing bonding jumper, the bonded subpanel and the two-wire circuit behind a three-prong receptacle.
  • Working as a journeyman: What journeyman electricians are expected to know and how the role grows.

Sources and further reading

Lessons are free study material. Finishing one does not certify a skill, count toward a license or replace hands-on training under qualified supervision.