Home > Electrical Learning Lab > Motor starters

Controls · Lesson · Intermediate · about 18 minutes

Motor Starters and Overload Protection

A motor starter is a contactor that switches the motor and an overload relay that protects it. Take one apart below, press START on a working control circuit and find out what each part does when something goes wrong.

Builds on Series and parallel circuits.

You will learn:

  • What a contactor, a coil, an auxiliary contact and an overload relay each do
  • How three-wire START and STOP control seals itself in
  • Why an overload trips after a delay and a short circuit clears at once
  • Reading a Class 10 trip curve
  • Finding the cause of a starter that will not start or will not stay running
What this model assumes
  • The supply holds its voltage and the three phases are balanced.
  • Running current follows the mechanical load in a simple way: full-load amps at nameplate load, more above it, with magnetizing current left at no load.
  • Starting current is six times full-load current and falls to the running value over two seconds.
  • The overload relay and the breaker follow smooth inverse-time curves with the shape of published class curves. Real devices publish their own time-current curves, and those are the ones to use on the job.
Understand

What a motor starter does

A motor is switched on and off by a contactor: a heavy-duty relay whose coil pulls a set of large contacts closed. A contactor on its own is a switch. Add an overload relay that watches the motor current and opens the control circuit when the motor runs too hot, and the pair becomes a motor starter. Most starters an electrician meets are this combination in one enclosure, in a motor control center bucket or in a combination starter with its own disconnect.

Motors need their own protection because of how they start. A motor at rest draws roughly six times its running current until it comes up to speed, for a second or two. A breaker sized to ride through that starting surge is far too big to notice the motor pulling 125 percent of its rated current for an hour, and that slow overload is exactly what burns out windings. So the circuit uses two devices: the breaker or fuses handle short circuits and ground faults, and the overload relay handles the motor's slow overheating.

This lesson uses a 10 horsepower, 460 volt, three-phase motor. Its full-load current is 14 A, its locked-rotor current is about 84 A, and it sits behind a 35 A inverse-time breaker and a Class 10 overload relay set to 14 A. Those numbers drive every drawing and every reading below.

Explore

Take a starter apart

The drawing below is a full-voltage starter the way it sits in an enclosure: the contactor on top, the overload relay bolted to its load side, a small control transformer beside it and the START and STOP station on the door. Switch to the exploded view to pull the pieces apart, and tap any piece, or its name in the list, to see what it does and where it fails.

Interactive: Inside a motor starter

An exploded view of a full-voltage motor starter: the contactor's coil, armature, three main contacts and auxiliary contact, the overload relay's three heater elements, trip contact, reset button and dial, the control transformer and the START and STOP station. Each piece is named and explained. The simulator runs in your browser with JavaScript turned on.

Two of these parts do most of the work and cause most of the confusion. The auxiliary contact is a small contact on the side of the contactor that moves with the main contacts. Wired in parallel with the START button it becomes the seal-in (or holding) contact that keeps the coil pulled in after your finger leaves the button. The overload relay carries the motor current through three heater elements. A sustained overload warms a bimetal strip or a sensing circuit until the relay's small trip contact opens, and that contact sits in series with the coil, so the contactor drops out and the motor stops.

Understand

Three-wire control: how START seals itself in

The control circuit is drawn as a ladder. The two vertical rails are the control voltage, usually 120 V from a small control transformer. Each horizontal rung is one path from the left rail to the right rail, and current flows across a rung only when every contact on it is closed.

  1. A control fuse protects the control wiring.
  2. The STOP button is normally closed. Current passes through it until someone presses it.
  3. The START button is normally open. It closes only while it is pressed.
  4. The contactor's auxiliary contact (M) sits in parallel with START. It is open while the contactor is dropped out.
  5. The M coil is the load on the rung.
  6. The overload relay contact (OL) is normally closed and opens only when the relay trips.

Press START and the rung completes: fuse, STOP, START, coil, OL contact. The coil pulls the contactor in. The main contacts close and start the motor, and the auxiliary contact closes beside the START button. Let go of START and the coil keeps its current through the auxiliary contact instead. That is the seal-in. Press STOP, or let the overload relay trip, and the rung opens anywhere along its length. The coil drops out, the auxiliary contact opens with it, and the circuit forgets it was ever running. The motor stays off until someone presses START again.

That last behavior has a name: low-voltage protection. If the power fails while the motor is running, the contactor drops out, and when power returns the motor does not restart on its own. A two-wire circuit, such as a float switch or a thermostat feeding the coil directly, gives low-voltage release instead: the motor restarts as soon as power returns and the switch is still closed. Which one a machine needs is a design decision, and it is why conveyors and saws use three-wire control while a sump pump often uses two-wire control.

Experiment

Run the starter

The simulator runs the control circuit and the power circuit together. Press START and watch the coil pull in, the main contacts close and the motor come up to speed while its current falls from the starting surge to the running value. Raise the mechanical load past 100 percent and the overload relay's thermal memory begins to climb. Pick a fault from the list to see how the circuit misbehaves, and speed time up when you are waiting on a slow overload.

Interactive: Motor starter control and power circuits

A working three-wire control circuit beside the three-phase power circuit it controls. START, STOP, a load setting from 0 to 200 percent of rated, a time control, and a list of faults: seal-in wire broken, control fuse blown, coil open, one phase lost, main contacts welded, short circuit at the motor. Readings show the current in each phase, the overload relay's thermal memory and the state of every device. The simulator runs in your browser with JavaScript turned on.

A few things worth trying. Set the load to 150 percent, press START and speed time up: the thermal memory climbs for a few minutes and then the relay trips, the coil drops out, and START does nothing until the relay is reset. Pick the lost phase: the motor will not start from rest, and if it was already running it keeps turning on two phases while drawing far more current on each of them, which is why the relay trips soon after. Pick the short circuit: the breaker opens before the relay's thermal element can warm at all.

Understand

Overload or short circuit? Two faults, two devices

Both faults are overcurrent, and that is where the similarity ends. An overload is more current than the equipment is rated for, flowing through its normal path: a motor dragging a jammed conveyor, a pump pushing against a closed valve, a motor fed on two phases. The current is perhaps 1.1 to 6 times normal, and the damage is heat that builds over seconds to minutes. A short circuit is current taking a path it should never take, from phase to phase or phase to ground. The current is limited only by the supply and the conductors, so it can be thousands of amps, and the damage is done in a fraction of a second.

The overload relay is an inverse-time device: more current, faster trip. Its trip class says how long it allows at six times its setting. A Class 10 relay opens within 10 seconds at 600 percent, a Class 20 within 20 seconds, a Class 30 within 30 seconds. Class 10 suits motors that reach speed quickly; Class 20 is the common general-purpose choice; Class 30 is for high-inertia loads that take a long time to accelerate. The relay in the simulator is Class 10.

Trip times from the lesson's Class 10 curve, relay set to 14 A
CurrentMultiple of settingTime to trip
14 A or less100 percentNever
16.8 A120 percentAbout 13 minutes
21 A150 percentAbout 5 minutes
28 A200 percentAbout 2 minutes
84 A600 percent10 seconds

Now put the 35 A breaker beside it. At 17.5 A, which is 125 percent of the motor's rating, the breaker sees half of its own rating and never trips, and the relay opens after about ten minutes. At the 84 A starting surge, the relay would trip in 10 seconds, but a normal start lasts two, so both devices ride through it. At a bolted fault of several thousand amps, the breaker's instantaneous element opens in about one cycle, long before the relay's thermal element could react. Each device covers the fault the other cannot.

A jammed conveyor

Given: Relay set to 14 A, Class 10; Motor stalls and draws locked-rotor current, 84 A

  1. Multiple of setting = 84 ÷ 14 = 6, or 600 percent
  2. Class 10 means a trip within 10 seconds at 600 percent

Answer: The overload relay trips in about 10 seconds; the 35 A breaker, at 2.4 times its rating, would take far longer

Solve

Find the fault

Starters fail in a handful of ways, and the symptom usually names the part. These three challenges use the same drawings and the same model as the simulator. Each one checks your answer at once.

Challenge: Find the part

The lesson names a part of the starter, such as the auxiliary contact or the overload relay's reset button, and you find it on the drawing or pick it from the list.

Challenge: Name the cause

Three symptoms, one at a time: a motor that runs only while START is held, a coil with voltage across it that will not pull in, a motor that hums on START and trips. Pick the cause, then see it in the simulator.

Challenge: Which device acts?

Three currents with their durations: 17.5 A for fifteen minutes, 84 A for two seconds, a 5,000 A fault. Decide whether the overload relay, the breaker or neither one opens.

One habit matters more than any single answer. An overload relay that has tripped is reporting a problem with the motor or its load. Find the cause before resetting it, and never hold it in, jumper its contact or fit a larger heater to make a nuisance trip go away. The relay is the only thing between a motor and a burned-out winding.

Apply

Where starters show up

Starters are everywhere a motor runs: rooftop units, pumps, fans, compressors, conveyors, machine tools and the rows of buckets in a motor control center. Industrial and commercial electricians wire them, set the overload relays from the nameplate, and spend a good share of their troubleshooting time on the control circuits around them.

The same ideas carry into newer equipment. A soft starter limits the starting surge electronically and a variable frequency drive controls speed, but both still need a disconnect, short-circuit protection and overload protection, and the drive's own overload function follows the same class curves. Understanding the electromechanical starter first makes the drive's parameter list read like an old friend.

If this is the kind of work you want more of, the related openings below are industrial and service roles where motor control is daily work.

Check your understanding

1. After you release the START button, what keeps the contactor coil pulled in?

Answer: The auxiliary (seal-in) contact in parallel with START. The auxiliary contact closes when the contactor pulls in and carries the coil current once START opens again.

2. A motor runs only while someone holds the START button. What is the most likely cause?

Answer: The seal-in circuit is open: the auxiliary contact or its wire. Every other fault stops the motor from starting at all. Only an open seal-in path lets it run while START is held and drop out when it is released.

3. The 14 A motor draws 17.5 A for fifteen minutes behind a 35 A breaker and a Class 10 relay set to 14 A. Which device opens?

Answer: The overload relay. 17.5 A is 125 percent of the relay setting, which trips after about ten minutes. It is half of the breaker's rating, so the breaker never sees an overload.

4. A bolted fault at the motor terminals pulls about 5,000 A. Which device clears it?

Answer: The breaker's instantaneous element, within about a cycle. A short circuit is the breaker's job. Its magnetic element opens in about one cycle, long before a thermal relay could respond.

5. What does a Class 10 rating on an overload relay mean?

Answer: It trips within 10 seconds at 600 percent of its setting. Trip class is the time allowed at six times the setting. Class 20 allows 20 seconds and Class 30 allows 30.

Where this knowledge gets used

  • Industrial openings: Motor control centers, starters, drives and the control circuits around them are the daily work of industrial electricians.
  • Service and repair openings: Service electricians spend much of their time finding why a motor will not start or will not stay running.
  • Working as a journeyman: What journeyman electricians are expected to know and how the role grows.

Sources and further reading

Lessons are free study material. Finishing one does not certify a skill, count toward a license or replace hands-on training under qualified supervision.