Fundamentals · Lesson · Intermediate · about 16 minutes
Transformers and Voltage
A transformer trades voltage for current through nothing but a shared magnetic field. Change the turns on the one below and watch the secondary voltage, the currents and the power respond the way the nameplate math says they should.
You will learn:
- What the turns ratio does to voltage and to current
- Why power in equals power out, and what that means for wire size
- Step-down, step-up and isolation transformers
- Reading a kVA nameplate and finding full-load current
- Where the ideal model stops: losses, inrush, regulation and DC
What this model assumes
- The transformer is ideal: no winding resistance, no core loss, no leakage flux and no magnetizing current, so the secondary voltage holds at any load and power in equals power out.
- An optional efficiency figure charges a fixed share of the output power to the primary as loss, which is a simplification of how real losses behave.
- Voltages and currents are RMS values on a sinusoidal supply. A transformer does nothing useful on steady direct current.
What a transformer does
A transformer is two coils of wire, a primary and a secondary, wound on a shared iron core. Alternating current in the primary builds a magnetic field in the core that grows, collapses and reverses, through sixty full cycles every second. That changing field passes through the secondary and induces a voltage in it. No current flows from one winding to the other. The energy crosses the core as a magnetic field, which is why a transformer also isolates the two circuits.
The size of the induced voltage depends on how many turns of wire the field passes through. Every turn on the core sees the same changing field, so every turn develops the same voltage: the volts per turn are the same on both windings. A secondary with a quarter of the primary's turns delivers a quarter of the voltage. A secondary with ten times the turns delivers ten times the voltage.
- Step-down: fewer turns on the secondary, lower voltage out. The 480 to 120 V control transformer in a motor starter, the pole transformer feeding a house.
- Step-up: more turns on the secondary, higher voltage out. The transformer at a power plant that raises generator voltage for the lines.
- Isolation: the same turns on both sides, the same voltage out. Used where a circuit must be separated from the source with no change in voltage.
The reason utilities transform at all is heat in the conductors. The power lost in a wire is current squared times resistance, so cutting the current by ten cuts the loss by a hundred. Sending power at high voltage and low current, then stepping it down near the load, is what makes a long run affordable.
Take a transformer apart
The drawing shows a small dry-type control transformer, the kind mounted inside a motor starter or a machine panel. Switch to the exploded view to pull the windings off the core, and tap any piece, or its name in the list, for what it does and how it is marked.
Interactive: Inside a control transformer
Two markings matter in the field. Primary terminals are marked H1, H2 and secondary terminals X1, X2; a transformer with several primary voltages adds H3 and H4, and taps let you correct for a supply that runs a little high or low. The nameplate gives the kVA rating, the primary and secondary voltages, the frequency, the temperature rise and the impedance. Everything you need to size the conductors and the overcurrent protection is on that plate.
The turns ratio
Write the primary quantities with a p and the secondary with an s. Because the volts per turn match, the voltages sit in the same ratio as the turns.
An ideal transformer passes power through without loss, so the volt-amperes on one side equal the volt-amperes on the other: Vp × Ip = Vs × Is. Put the two facts together and the currents sit in the opposite ratio to the voltages. The side with the lower voltage carries the higher current, which is why the secondary of a step-down transformer is wound with heavier wire.
A 480 to 120 V control transformer
Given: 480 V on the primary; 400 primary turns, 100 secondary turns; The control circuit draws 10 A
- Vs = Vp × Ns ÷ Np = 480 × 100 ÷ 400 = 120 V
- Ip = Is × Ns ÷ Np = 10 × 100 ÷ 400 = 2.5 A
- Check: 480 × 2.5 = 1,200 VA in, 120 × 10 = 1,200 VA out
Answer: 120 V on the secondary, 2.5 A on the primary
Winding a doorbell transformer
Given: 120 V supply; 100 primary turns; 24 V wanted on the secondary
- Ns = Np × Vs ÷ Vp
- Ns = 100 × 24 ÷ 120
Answer: 20 secondary turns
The ratio is usually quoted the way the voltages are, primary first: a 480 to 120 V unit is a 4 to 1 transformer. Reverse the connections and the same unit becomes a 1 to 4 step-up, which is exactly what happens, by accident, when a secondary is back-fed.
Wind one yourself
The simulator lets you set the primary voltage, wind both coils a turn at a time and connect a load. The meters show both voltages and both currents, and the power on each side, so you can watch the ratio hold at every setting. Pick a preset to jump to a transformer you have met on the job, and switch the model from ideal to 96 percent efficient to see where the extra primary current goes.
Interactive: Transformer workbench
Things worth trying. Halve the secondary turns and watch the secondary voltage halve while the secondary current, for the same load, halves too, so the power drops to a quarter. Set the two windings equal for an isolation transformer. Pick the pole transformer preset, 7,200 V to 240 V, and notice that a 30 to 1 ratio turns a 10 A load into a third of an amp on the primary. Then switch on the losses and watch the primary current rise while the secondary stays where it was.
Reading the nameplate: kVA and full-load current
Transformers are rated in kilovolt-amperes, kVA, because the transformer heats according to the current it carries whatever the power factor of the load. Full-load current on either side is the kVA divided by that side's voltage.
A 25 kVA pole transformer
Given: 25 kVA; 240 V secondary
- I = 25 × 1,000 ÷ 240
- I = 25,000 ÷ 240
Answer: 104 A at full load
A 3 kVA control transformer
Given: 3 kVA; 120 V secondary
- I = 3 × 1,000 ÷ 120
Answer: 25 A at full load
| Where you meet it | Primary | Secondary | Ratio |
|---|---|---|---|
| Control transformer in a starter | 480 V | 120 V | 4 to 1 |
| Doorbell or thermostat | 120 V | 24 V | 5 to 1 |
| Buck transformer for 208 V equipment | 240 V | 208 V | 15 to 13 |
| Pole transformer feeding a house | 7,200 V | 240 V | 30 to 1 |
| Step-up to a medium-voltage motor | 480 V | 4,160 V | 3 to 26 |
| Isolation transformer | 120 V | 120 V | 1 to 1 |
The pole transformer's 240 V secondary is center-tapped, and the tap is the grounded neutral of a house service. Each half of the winding gives 120 V to the neutral, and the whole winding gives 240 V across the two hot conductors. That one tap is why a home has both voltages from one transformer.
Where the ideal model stops
The simulator's transformer is perfect. Real ones are close, usually 95 to 99 percent efficient, and the differences are worth knowing because they show up as heat, as nuisance trips and as readings that do not match the formula.
- Magnetizing current. A real primary draws a small current with nothing connected to the secondary, to keep the core magnetized. It is a few percent of full-load current and it is why an unloaded transformer still hums and runs warm.
- Core losses. The changing field heats the steel through eddy currents and hysteresis. Cores are built from thin insulated laminations to limit the eddy currents, and those laminations are what you see on the edge of the core.
- Copper losses. The windings have resistance, so they heat in proportion to current squared. This is the loss that grows with load.
- Voltage regulation. Winding resistance and leakage reactance drop some voltage under load, so the secondary sags a little as current rises. The nameplate impedance, a few percent, tells you how much and also sets the fault current the secondary can deliver.
- Inrush. Energizing a transformer can draw ten or more times its rated current for a few cycles while the core finds its working flux. Primary protection is sized to ride through it, which is work for qualified people following the nameplate and the code.
- Frequency. Core flux follows volts per hertz. A 60 Hz unit on a 50 Hz supply at the same voltage runs its core at 120 percent flux and overheats; the same unit at 400 V and 50 Hz is back at its rated flux.
None of this changes the turns-ratio math. It adds a little loss and a little sag on top of it, and the nameplate tells you how much to expect.
Work the numbers
Three challenges, each checked against the same model as the workbench.
Challenge: Find the part
The lesson names a part of the control transformer, such as the X1 terminal or the primary winding, and you find it on the drawing or pick it from the list.
Challenge: Wind for 120 volts
The primary has 120 turns on a 480 V supply. Set the secondary turns so the secondary reads exactly 120 V.
Challenge: Find the currents
A 480 to 120 V control transformer feeds a 10 A load: what does the primary draw? And what is the full-load secondary current of a 3 kVA, 120 V unit?
Where transformers show up
Every motor starter with a 120 V control circuit has a control transformer in it, which is where the motor starter lesson left off. Commercial buildings take a 480Y/277 V service and use dry-type transformers to make 208Y/120 V for receptacles, which is the three-phase arithmetic in the next lesson. Services, generators, elevator rooms, sign circuits and machine panels all have one.
Electricians who install and connect transformers size the primary and secondary conductors and protection from the nameplate, set the taps to match the measured supply voltage, torque the terminals, and check the secondary voltage and the phase rotation before anything downstream is energized. Those checks are qualified work on energized equipment, done with rated meters and the right protective equipment.
If this is the work you want more of, the openings below are commercial and industrial roles where transformers are part of the daily job.
Check your understanding
1. A transformer has 400 primary turns and 100 secondary turns. With 480 V on the primary, what is the secondary voltage?
Answer: 120 V. Vs = Vp × Ns ÷ Np = 480 × 100 ÷ 400 = 120 V. A quarter of the turns gives a quarter of the voltage.
2. That same 4 to 1 transformer delivers 10 A at 120 V. Ignoring losses, what current does the primary draw?
Answer: 2.5 A. Power in equals power out: 1,200 VA ÷ 480 V = 2.5 A. Currents run in the opposite ratio to the voltages.
3. A transformer has more turns on the secondary than on the primary. What kind is it?
Answer: Step-up. More secondary turns means more volts per the same volts per turn, so the voltage goes up.
4. What is the full-load current of a 25 kVA, 240 V single-phase transformer?
Answer: 104 A. I = kVA × 1,000 ÷ V = 25,000 ÷ 240 = 104 A.
5. Why does a transformer do nothing useful on steady direct current?
Answer: A steady current makes a steady field, and only a changing field induces a voltage in the secondary. Induction needs a changing magnetic field. With steady DC the field settles and the secondary shows nothing, while the primary overheats.
Where this knowledge gets used
- Commercial openings: Commercial electricians set, connect and test the dry-type transformers that make 208Y/120 V in offices, schools and retail buildings.
- Industrial openings: Plants run on transformers from the service entrance down to the control transformer in every starter.
- Moving up to foreman: What foremen are expected to know and how to get there.
Sources and further reading
Tony R. Kuphaldt (ibiblio)
Lessons In Electric Circuits (six volumes)Transformer theory, Volume II chapter 9.
Global, physics and circuit theory; US examples. Volume editions dated per volume (DC 5th, AC 6th).
Schneider Electric
Electrical Installation Guide (wiki)Transformer selection and protection, in IEC terms.
IEC and international; not the US NEC. Living wiki; chapters dated per page (IEC 60364-4-42 2024 update noted on the main page).
National Fire Protection Association
NFPA 70, National Electrical Code (NEC)Article 450 transformer overcurrent protection.
United States; adopted by jurisdiction. 2026 edition issued August 2025; the 2023, 2020 and 2017 editions remain in force in many states; each state adopts its own edition and amendments.